BIS Menu  |  Electrical Inspection Work Order  |  Plumb. Inspections  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M393749
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 105 CROSBY STREET MANHATTAN BIN: 1007557     Block: 496   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 70 PRINCE ST Census Tract:   43 Health Area:  6800
CELLAR. 1ST, 2ND, ROOF Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
Special Place Name:   DIG INN
DOB Cross Street(s):   LAFAYETTE STREET,    CROSBY STREET
Status:   C - JOB IS SIGNED OFF 12/07/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/22/2017 1:28 PM
Application Entered:   03/22/2017 Job Start Date:   03/22/2017
Last Change:   12/07/2017 Job End Date:   11/30/2017
Appointment Status:   
Last Inspection By:   VINCENT CASTALDO       On     10/18/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012776 Licensee Name: HERNAN F SOCARRAS
Firm: 003646 Firm Name: HESO ELECTRICAL INC
Firm Phone: 718-204-8568  Firm Address: 3418 NORTHERN BLVD, STE 4-5 LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $875.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PETER HOFFMAN
Owner Business Name: N/A
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  600A 3PH
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  3 SETS OF 2AWG
B. Over #2 to 1/0  1  1 SET 3/O AWG
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  4  4 SETS 350 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  4  3-100A, 1-200A
D. 3 Phase Over 225 AMPS  1  600A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL      10      36     
001    33  42    12  67             
002    25  18    51             
ROF      12         
Buildings Total 64  65    24  129     12     36      
Total Units : 330 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/22/2017 Notice: 1 - FIRST NOTICE 10/02/2017
Power Issued: 03/22/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M393749
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/29/2017 10/02/2017 STP V (60) (7)
INSPECTION COMMENTS: FAIL. FIXTURES, HEATERS AND ALL MOTORS NOT FILED FOR. DID NOT INSPECT AC EQUIPMENT.
 
(2) 10/18/2017 10/18/2017 VTC C R (58) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M393749
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 001) 10 AWG ON 40 AMP CIR BK 240.4
RSLV 09/29/2017 09/29/2017 10/18/2017
 
002 (999) OTHER
(FLOOR: 001) COVER MISSING KITCHEN 2 GANG 314.25
RSLV 09/29/2017 09/29/2017 10/18/2017
 
003 (999) OTHER
(ALL FLOORS) DIRECTORY PUT IN ALL PANELS 408.4
RSLV 09/29/2017 09/29/2017 10/18/2017
 
004 (999) OTHER
(BASEMENT) PULLBOX TO SMALL BOTTOM METER 314.28
RSLV 09/29/2017 09/29/2017 10/18/2017
 
005 (999) OTHER
(BASEMENT) HANDLE TIES NEEDED SMALL PANEL 210.4
RSLV 09/29/2017 09/29/2017 10/18/2017
 
006 (999) OTHER
(BASEMENT) TEMP NOT REMOVED CEILING 590.3
RSLV 09/29/2017 09/29/2017 10/18/2017
 
007 (999) OTHER
(BASEMENT) KO OPEN METER 110.12
RSLV 09/29/2017 09/29/2017 10/18/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.