Electrical Application Details for App #: Z136789
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 326 FT WASHINGTON AVENUE MANHATTAN BIN: 1063504     Block: 2142   Lot: 161
   
Application Completed and Certified

Filed: 336 FT WASHINGTON AV Census Tract:   263 Health Area:  0300
GROUND FL Admin Area:   Z - UPPER MANHATTAN Inspection Area:   A
NEW YORK, NY 10033 Community Board:   112
Special Place Name:   APT 1A
DOB Cross Street(s):   WEST 174 STREET,    WEST 175 STREET
Status:   C - JOB IS SIGNED OFF 03/29/2013
Request Type:   P - PICK-UP eFiled:   YES
Application Entered:   10/23/2012 Job Start Date:   10/24/2012
Last Change:   03/29/2013 Job End Date:   11/29/2012
Appointment Status:    Complaint Number:    1306440
Last Inspection By:   KEMPF, JOHN       On     03/13/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010443 Licensee Name: CARDINAL HESCOTT
Firm: 000858 Firm Name: LEKTRIC INSTALLATIONS COR
Firm Phone: 718-469-3200  Firm Address: 3802 CHURCH AVENUE BROOKLYN NY 11203 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $88.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: NEWCASTLE REALTY SERVICES
Authorized Representative:  MICHAEL ZAUBERMAN
Relationship To Owner:   MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  12/24 CIRCUIT PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  1A  21             
Buildings Total 21                
Total Units : 46 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/27/2013
Power Issued: Response: F - FILED TO REMOVE OBJECTION 10/23/2012

Follow-Up: X - FILED APPL,NOW CLOSED 10/23/2012
Contractor's Comments:  THROUGHOUT THE APT. 1A

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: Z136789
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/10/2012 09/19/2012 RID W (30) (2)
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 02/15/2013 02/27/2013 MFF A R (80) (2) Y
INSPECTION COMMENTS: *SEE OBJECTIONS
 
(3) 03/13/2013 03/23/2013 JKF C R (30) (0) Y
INSPECTION COMMENTS: *UNIT 1A*

OBJECTION FOR APPLICATION #: Z136789
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
THROUGHOUT THE APT. 1A FIRST FLOORCOM: SUB PANEL, BANCH CIRCUIT WIRING, RECEPTACLES OUTLETS, SWITCHES
RSLV 09/10/2012 09/10/2012 02/15/2013
 
002 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
FIXTURES. THIS IS NOT A FINAL INSPECTION. SEE THE COMPLAINT#1306440
RSLV 09/10/2012 09/10/2012 02/15/2013
 
003 (999) OTHER
1A: TWO POLE BREAKER NOT INSTALLED ON 3 WIRE BX..... - 210.4(B)
RSLV 02/15/2013 02/15/2013 03/13/2013
 
004 (999) OTHER
1A: NEUTRAL AND CIRCUITS NOT GROUPED TOGETHER..... - 210.4(D)
RSLV 02/15/2013 02/15/2013 03/13/2013