Premises: 976 TINTON AVENUE BRONX BIN: 2004826     Block: 2669   Lot: 9
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 976 TINTON AV Census Tract:   133 Health Area:  3500
ENTIRE BSMT Admin Area:   Y - BRONX Inspection Area:   C
BRONX, NY 10456 Community Board:   203
Special Place Name:   THE ENTIRE BSMT
DOB Cross Street(s):   EAST 163 STREET,    EAST 165 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   P - PICK-UP eFiled:   YES
Application Entered:   03/07/2014 Job Start Date:   03/07/2014
Last Change:   08/22/2025 Job End Date:   12/31/2014
               COMPLETION FEE WAS BILLED
Appointment Status:    Complaint Number:    2193900
Last Inspection By:   GIUSEPPE IMBURGIA       On     05/07/2016      
Field Disp:   H - NO PROGRESS ON JOB
Energize Recommendation:  
Objection Disposition:  X - NOT REMOVED

License #: 009841 Licensee Name: RONALD TWITTY
Firm: 002787 Firm Name: SHALLY ELECTRICAL CO. INC
Firm Phone: 718-782-2020  Firm Address: 611 GRAND STREET BROOKLYN NY 11211 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $40.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: TINTON 976 REALTY LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                     
Buildings Total                     
Total Units : 6 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: C - CALL TO OFFICE 05/10/2016
Power Issued: Response: F - FILED TO REMOVE OBJECTION 03/07/2014

Follow-Up: F - FILED TO REMOVE OBJECTION 03/07/2014
Contractor's Comments:  REMOVE ELECTRICAL VIOLATIONS

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: Y167187
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/15/2014 01/22/2014 RID W (15) (17)
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 04/23/2016 04/25/2016 GIG N (2) (0) Y
INSPECTION COMMENTS: CONTRACTOR CANCELED
 
(3) 05/07/2016 05/10/2016 GIG H X (30) (0) Y
INSPECTION COMMENTS: FAIL NO PROGRESS ON PAST OBJECTIONS .

OBJECTION FOR APPLICATION #: Y167187
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
BMST SERVICE EQUIPMENTCOM: 200 AMP SERVICE SWITCH, SERVICE ENTRANCE CONDUCTOR
OPEN 01/15/2014 01/15/2014
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BSMT GROUND CONDUCTORCOM: NO WATER MAIN GROUND PROVIDED
OPEN 01/15/2014 01/15/2014
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BSMT SERVICE EQUIPMENTCOM: SERV, ENTRANCE CONDUCTOR, SERVICE SWITCH NEUTRAL BAR NOT BONDED
OPEN 01/15/2014 01/15/2014
 
004 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
TO ENCLOSURE
OPEN 01/15/2014 01/15/2014
 
005 (999) OTHER
BSMT SERVICE SWITCH. 230COM: SERVICE SWITCH NOT PROPER SIZE
OPEN 01/15/2014 01/15/2014
 
006 (999) OTHER
BSMT SERVICE CONDUCTOR NOT PROPER SIZE. 230
OPEN 01/15/2014 01/15/2014
 
007 ( 19) DEFECTIVE WIRING IS IN USE
THE ENTIRE BSMTCOM: DEFECTIVE OPEN WIRING ARE IN USE
OPEN 01/15/2014 01/15/2014
 
008 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
DEFECTIVE RECEPTACLE ARE IN USE
OPEN 01/15/2014 01/15/2014
 
009 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
DEFECTIVE LIGHTING FIXTURES ARE IN USE
OPEN 01/15/2014 01/15/2014
 
010 ( 17) DEFECTIVE SWITCHES ARE IN USE
DEFECTIVE SWITCH ARE IN USE
OPEN 01/15/2014 01/15/2014
 
011 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
ARMORED CABLES ARE NOT PROPERLY SECURED
OPEN 01/15/2014 01/15/2014
 
012 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
ARMORED CABLES ARE NOT PROPERLY TERMINATED
OPEN 01/15/2014 01/15/2014
 
013 ( 29) OUTLET BOXES ARE NOT COVERED
OUTLETS BOXES ARE NOT COVERED
OPEN 01/15/2014 01/15/2014
 
014 ( 39) MOTOR NOT PROVIDED WITH PROPER RUNNING PROTECTION
OUTLETS BOXES ARE NOT SECURED
OPEN 01/15/2014 01/15/2014
 
015 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
KNOCKOUTS ARE NOT CLOSED IN OUTLETS BOXES
OPEN 01/15/2014 01/15/2014
 
016 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
KNOCKOUTS ARE NOT CLOSED IN PANEL BOXTHIS IS NOT A FINAL INSPECTION. SEE THIS COMPLAINT #2193900
OPEN 01/15/2014 01/15/2014
 
017 (999) OTHER
"VERY DANGEROUS AND HAZARDOUS CONDITION"
OPEN 01/15/2014 01/15/2014