Electrical Application Details for App #: M337024
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 53 5 AVENUE MANHATTAN BIN: 1009373     Block: 570   Lot: 7501
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 55 5 AV Census Tract:   61 Health Area:  5700
SUITE 1703 Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
DOB Cross Street(s):   EAST 12 STREET,    EAST 13 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/15/2013 3:52 PM
Application Entered:   02/15/2013 Job Start Date:   02/16/2013
Last Change:   08/22/2025 Job End Date:   02/09/2014
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   BINGEL, LORI       On     05/28/2013      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  

License #: 012324 Licensee Name: GERBERT BONHOMME
Firm: 004105 Firm Name: SUPREME ELECTRIC CORP
Firm Phone: 718-658-1078  Firm Address: 107-54 SUTPHIN BLVD JAMAICA NY 11435 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $44.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BUSINESS BUSINESS
Owner Business Name: TRULIA INC.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
017  1703               
Buildings Total                 
Total Units : 29 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 06/07/2013
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  MINOR INTERIOR RENOVATION INSTALLING A FEW LIGHTS $ OUTLET

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M337024
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/28/2013 06/07/2013 LBI A (30) (4) Y
INSPECTION COMMENTS: *ALL OBJECTIONS PERTAIN TO FURNITURE FEED JUNCTION BOXES,ALL WERE WIRED DEFECTIVELY* **SEE OBJECTIONS
 
(2) 06/12/2013 06/22/2013 MFF Z (0) (0) Y
INSPECTION COMMENTS: *CANCELED*

OBJECTION FOR APPLICATION #: M337024
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (315) CONDUCTORS NOT PROPERLY IDENTIFIED
1703: 12/2 BX NEUTRAL TAPED GREEN...... - 200.6,250.119
OPEN 05/28/2013 05/28/2013
 
002 (328) CIRCUIT CONDUCTORS NOT GROUPED
1703: 12/2 BX USING NEUTRAL IN CABLE AS HOT RETURN... - 300.20
OPEN 05/28/2013 05/28/2013
 
003 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
1703: NEW FURNITURE NOT PROPERLY GROUNDED AT J-BOX.... - 250.134
OPEN 05/28/2013 05/28/2013
 
004 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
1703: NEUTRAL AND EQUIP.GRND CONNECTED THROUGH-OUT... - 250.24A5
OPEN 05/28/2013 05/28/2013