BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z131507
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 125 WEST 78 STREET MANHATTAN BIN: 1030250     Block: 1150   Lot: 21
   
Application Completed and Certified

Filed: 125 W 78 ST Census Tract:   165 Health Area:  3500
SERVICE WORK Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10024 Community Board:   107
DOB Cross Street(s):   COLUMBUS AVENUE,    AMSTERDAM AVENUE
Status:   C - JOB IS SIGNED OFF 02/28/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/10/2011 6:21 PM
Application Entered:   08/10/2011 Job Start Date:   08/11/2011
Last Change:   02/28/2012 Job End Date:   12/01/2011
Appointment Status:   
Last Inspection By:   BEST, J       On     02/02/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012302 Licensee Name: MAYER WEBER
Firm: 004070 Firm Name: METRO ELEC'L CONTRS, INC
Firm Phone: 718-439-7466  Firm Address: 218 HAMILTON AVENUNE BROOKLYN NY 11231 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $190.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JEGER MEYER
Owner Business Name: WEST 78 STREET REALTY LLC
Authorized Representative:  S SILBER
Relationship To Owner:   CONT.


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 6 #4-Wire 0 #10-Wire 0
Existing Meters 6 + New Meters 6 - Removed Meters 6 = Total Meters 6

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/10/2011 Notice: 1 - FIRST NOTICE 12/07/2011
Power Issued: 08/10/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: Z131507
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/29/2011 12/07/2011 TJ1 A E (45) (2) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 01/09/2012 01/21/2012 WMK N (15) (0) Y
INSPECTION COMMENTS: CONTR COULD NOT PROVIDE LEGAL SAFE ACCESS TO BASEMENT
 
(3) 02/02/2012 02/15/2012 JSB C R E (35) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z131507
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
BSMT: PL+P PANEL (NO MAIN BREAKER PROVIDED).... - ART.240.3
RSLV 11/29/2011 11/29/2011 02/02/2012
 
002 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
BSMT: S/S (1 1/4" KO MISSING)...... - 110.12(A)
RSLV 11/29/2011 11/29/2011 02/02/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order