Electrical Application Details for App #: M398498
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 433 EAST 52 STREET MANHATTAN BIN: 1040155     Block: 1364   Lot: 22
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 435 E 52ND ST Census Tract:   86.03 Health Area:  5000
E 52ND ST/FL 13/APT 13A Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10022 Community Board:   106
DOB Cross Street(s):    1 AVENUE,    DEAD END
Status:   C - JOB IS SIGNED OFF 12/19/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/13/2017 10:33 AM
Application Entered:   07/13/2017 Job Start Date:   07/14/2017
Last Change:   12/19/2017 Job End Date:   07/14/2018
Appointment Status:   
Last Inspection By:   SCHULER, THOMAS       On     12/18/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012209 Licensee Name: ANTHONY COSCHIGANO III
Firm: 003925 Firm Name: ECNY ELEC'L CONTR'S, INC
Firm Phone: 212-695-9084  Firm Address: 42 WEST 38TH STREET-STE 501 NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $134.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JEREMY JACOBS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
013  13A  11      373         
Buildings Total 11         373           
Total Units : 388 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/29/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M398498
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/28/2017 11/29/2017 TUR V (45) (3)
INSPECTION COMMENTS: OBJECTIONS ISSUED, AND CONTRACTOR MUST CORRECT APPLICATION DETAILS (SEE YOUR DETAILS)
 
(2) 12/18/2017 12/19/2017 TUR C R (50) (0)
INSPECTION COMMENTS: NO OBJECTIONS ALL CORRECTIONS MADE ON SITE AND APP ADJUSTED

OBJECTION FOR APPLICATION #: M398498
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(FLOOR: 013) 240.3 OCP FOR THE NEW AC UNITS OVER FUSED
RSLV 11/28/2017 11/28/2017 12/18/2017
 
002 ( 31) MORE THAN ALLOWABLE # OF CONDUCTORS ARE IN OUTLET BOX
(FLOOR: 013)314.16 ALL BOXES THAT NEW OUTLETS WERE FED FROM BOX FILL IS OVERFILLED MUST CHANGE BOX FOR CORRECT FILL (FOR ALL THE NEW 10 OUTLETS)
RSLV 11/28/2017 11/28/2017 12/18/2017
 
003 (999) OTHER
(FLOOR: 013)440. DISCONNECT FOR CEILING AC UNITS NOT SECURED 3PHASE GUEST BATHAND SIMILAR
RSLV 11/28/2017 11/28/2017 12/18/2017