Electrical Application Details for App #: Z130603
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 421 WEST 47 STREET MANHATTAN BIN: 1026562     Block: 1057   Lot: 21
   
Application Completed and Certified

Filed: 425 W 47 ST Census Tract:   127 Health Area:  4700
SERVICE ROOM Admin Area:   Z - UPPER MANHATTAN Inspection Area:   F
NEW YORK, NY 10036 Community Board:   104
DOB Cross Street(s):    9 AVENUE,    10 AVENUE
Status:   C - JOB IS SIGNED OFF 09/20/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/07/2011 10:10 AM
Application Entered:   06/07/2011 Job Start Date:   06/07/2011
Last Change:   09/20/2012 Job End Date:   06/07/2012
Appointment Status:   
Last Inspection By:   BEST, J       On     08/01/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010851 Licensee Name: RONALD J TESTA, JR.
Firm: 001416 Firm Name: TESTA ELECTRIC CO., INC
Firm Phone: 718-331-2747  Firm Address: 1435 65TH STREET, 2ND FL BROOKLYN NY 11219 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
009514 TESTA, RONALD 001416 TESTA ELECTRIC CO., INC RESPONSIBLE REP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $980.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: FOUNTAIN HOUSE
Authorized Representative:  KEN PHUNG
Relationship To Owner:   PROJECT MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  1  2000 AMP SWITCH
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  SETS OF 3/0 WIRE
D. Over 250 MCM  5  SETS 500
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  42 CIRCUITS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/07/2011 Notice: 1 - FIRST NOTICE 07/31/2012
Power Issued: 06/07/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW ELECTRICAL SERVICE FOR BUILDING. RUN RISERS FOR GENERATOR AND PICK UP EXISTING LOADS.

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: Z130603
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/05/2012 07/31/2012 CJH A E (60) (10) Y
INSPECTION COMMENTS: NOT FINAL
 
(2) 08/01/2012 08/13/2012 JSB C R E (90) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z130603
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
ELECTRIC RM CEILING 6X6 JUNCTIONHAS NO COVER 314-28C
RSLV 07/05/2012 07/05/2012 08/01/2012
 
002 ( 55) CONDUCTORS SMALLER THAN 1/0 AWG HAVE BEEN RUN IN PARALLEL
ELECTRIC RM KO ARE NOT CLOSED CEILING OUTLET BOXES
RSLV 07/05/2012 07/05/2012 08/01/2012
 
003 ( 29) OUTLET BOXES ARE NOT COVERED
ELECTRIC RM OUTLET BOXES ARE NOT COVERED TOP OF SW
RSLV 07/05/2012 07/05/2012 08/01/2012
 
004 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
ELECTRIC RM ARMORED CABLE NOT PROPERLY SECURED
RSLV 07/05/2012 07/05/2012 08/01/2012
 
005 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
ELECTRIC RM CONDUCTORS ARE NOT PROPERLY COLOR CODED FROM 12X12SPLICE BOX TO 200A PANEL(CONDUCTORS TAPE)
RSLV 07/05/2012 07/05/2012 08/01/2012
 
006 (999) OTHER
ELECT RM DOUBLE LUGGING IN 12X24 PLICE BOX 110.14A
RSLV 07/05/2012 07/05/2012 08/01/2012
 
007 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
ELECTRIC RM SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
RSLV 07/05/2012 07/05/2012 08/01/2012
 
008 (999) OTHER
ELE RM GROUNDING ELECTRODE CONDUCTOR NOT CONTINOUS 250.64(C)
RSLV 07/05/2012 07/05/2012 08/01/2012
 
009 (999) OTHER
ELECTRIC RM NO FUSE COORDINATION EXISTS DSW 240.12A
RSLV 07/05/2012 07/05/2012 08/01/2012
 
010 ( 29) OUTLET BOXES ARE NOT COVERED
ELECTRIC RM TROUGH COVER MISSINGS TOP OF SERVICE
RSLV 07/05/2012 07/05/2012 08/01/2012