BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M192876
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 301 EAST 40 STREET MANHATTAN BIN: 1038645     Block: 1333   Lot: 1
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 305 E 40 ST Census Tract:   88 Health Area:  5000
064191 APT 15A -15M Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10016 Community Board:   106
DOB Cross Street(s):    2 AVENUE,    QUEENS MIDTOWN TUNNEL APPROACH
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   08/30/2000 Job Start Date:   08/28/2000
Last Change:   08/22/2025 Job End Date:   09/08/2000
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     02/12/2019      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  X - NOT REMOVED

License #: 010312 Licensee Name: STEVEN MICHAELOFF
Firm: 002980 Firm Name: ALLRAN ELEC. OF N.Y. INC.
Firm Phone: 718-658-5005  Firm Address: 257 51 STREET BROOKLYN NY 11220 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $48.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: ALBERT HARVY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 20                  
Total Units : 44 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: C - CALL TO OFFICE 02/13/2019
Power Issued: Response: W - OBJ TO BE REMOVED 12/10/2001

Follow-Up:
Contractor's Comments:  2ND AVE & 40TH STREET

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M192876
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/08/2000 11/13/2000 PGR V (60) (2)
INSPECTION COMMENTS: NO COMMENT
 
(2) 02/12/2019 02/13/2019 TOR V X (10) (6)
INSPECTION COMMENTS: FAIL

OBJECTION FOR APPLICATION #: M192876
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
BREAK BLANK NO COMMENT
OPEN 11/08/2000 11/08/2000
 
002 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
PANEL NO COMMENT
OPEN 11/08/2000 11/08/2000
 
003 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 015) INTERNAL PARTS OF PANEL MOUNTED ON WOOD
OPEN 02/12/2019 02/12/2019
 
004 (294) PANEL IS LOCATED IN BATHROOM
(FLOOR: 015) MASTER BATHROOM
OPEN 02/12/2019 02/12/2019
 
005 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(FLOOR: 015) T-OUT
OPEN 02/12/2019 02/12/2019
 
006 ( 42) BUSHINGS ARE MISSING OR LOOSE
(FLOOR: 015) PANEL
OPEN 02/12/2019 02/12/2019
 
007 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 015) BATHROOM
OPEN 02/12/2019 02/12/2019
 
008 (999) OTHER
(FLOOR: 015) RECEPTACLES NOT TR TYPE 406.11
OPEN 02/12/2019 02/12/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order