Electrical Application Details for App #: M402473
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 1210 2 AVENUE MANHATTAN BIN: 1044389     Block: 1438   Lot: 51
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 1210 2 AV Census Tract:   110 Health Area:  4900
MULTI FLOOR Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10065 Community Board:   108
Special Place Name:   NY AMBULATORY
DOB Cross Street(s):   EAST 63 STREET,    EAST 64 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/06/2017 10:27 AM
Application Entered:   10/06/2017 Job Start Date:   10/07/2017
Last Change:   08/22/2025 Job End Date:   07/11/2019
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   ALGERNON CHARLES       On     09/06/2019      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 010949 Licensee Name: STUART MOSKOWITZ
Firm: 002795 Firm Name: MATROS AUTOMATED ELEC'L C
Firm Phone: 718-482-1000  Firm Address: 5-33 50TH AVENUE LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $2,617.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: CONSTRUCTTOMICS
Authorized Representative:  GLEN LEVY
Relationship To Owner:   CONSTRUCTION MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  11  6X#6THHN, 5X#2THHN
B. Over #2 to 1/0  2  2X1/0 THHN
C. Over 1/0 to 250 MCM  6  2X1/0, 2X3/0, 2X4/0
D. Over 250 MCM  3  2X600MCM, 2X350MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  18  7X60A, 4X100A, 1X175A, 6X
D. 3 Phase Over 225 AMPS  5  2X400A, 2X800A, 1X600A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  150A, 175A
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  60A

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    20  13    26  12         
BAS    120  74    41  163         
GND    132  72    25  150         
MEZ    12    12         
002    34  22    14  70  24  250     
Buildings Total 318  183    83  421     280         
Total Units : 1290 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 09/06/2019
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M402473
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/05/2019 06/06/2019 CDX V (265) (15)
INSPECTION COMMENTS: FAIL.
 
(2) 09/06/2019 09/06/2019 AYC V Y (133) (4)
INSPECTION COMMENTS: FAIL. OBJECTIONS ISSUED. OBSERVED: 6 SETS 600; 6 SETS 350, 2 SETS 4/0-4; 1 SET 3/0-4; 2 SETS 2/0; 4 SETS 1/0-4; 4 SETS #2/4; AND 9 SETS #6/4; 8 MOTORS( TOTAL 144 HP)

OBJECTION FOR APPLICATION #: M402473
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(FLOOR: 002)FLOOR 2 358.30 EMT 2 1/2 INCHES ARE NOT PROPERLY SUPPORTED (GENERATOR ROOM)
RSLV 06/05/2019 06/05/2019 09/06/2019
 
002 (999) OTHER
(ALL FLOORS) APP DOES NOT MATCH . ( AMOUNT OF FEEDERS)
OPEN 06/05/2019 06/05/2019
 
003 (999) OTHER
(ALL FLOORS)GND AND 2ND FLOOR 110.2(A) MEDICAL GASES ( NEEDS APPROVAL LETTERFOR LUMINARIES AND ELECTRICAL EQUIPMENT INSTALLED INSIDE OF MEDICALGASES)
OPEN 06/05/2019 06/05/2019
 
004 (999) OTHER
(ALL FLOORS) ELEVATOR NEEDS FULL INSPECTION ( NO ACCESS)
OPEN 06/05/2019 06/05/2019
 
005 (255) NO FUSE COORDINATION EXISTS
(BASEMENT) BSMT AM 240.12 (A) APPROVAL SERVICE FUSE COORDINATION
OPEN 06/05/2019 06/05/2019
 
006 (999) OTHER
(BASEMENT)BSMT 250.53 NOT PROVIDED SUPPLEMENTAL ELECTRODE ( SPRINKLER PIPE)
RSLV 06/05/2019 06/05/2019 09/06/2019
 
007 (999) OTHER
(BASEMENT)BSMT 408 .36 NOT PROVIDED INDIVIDUAL PROTECTION OVER 42 OVERCURRENTDEVICES. ( PANEL : LL-C SEC-1 , LL-C SEC-2/ ELL-CR-V)
RSLV 06/05/2019 06/05/2019 09/06/2019
 
008 (999) OTHER
(BASEMENT) BSMT DOES NOT FILE FOR ELECTRICAL METER / # 10 WIRE
OPEN 06/05/2019 06/05/2019
 
009 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(CELLAR) CELLAR 408.4 PANEL DIRECTORY INCOMPLETE ( PANEL ELL-CR-ISO)
RSLV 06/05/2019 06/05/2019 09/06/2019
 
010 ( 53) GFCI HAS NOT BEEN PROVIDED
(CELLAR)CELLAR 210.8 NOT PROVIDED GFCI ( JANITOR ROOM/ SURGICAL ATTIRE ROOM) T-OUT
RSLV 06/05/2019 06/05/2019 09/06/2019
 
011 (999) OTHER
(CELLAR)CELLAR . 110.3 EMERGENCY LUMINARIES BALLAST ARE NOT SUPPORTED (DROP CEILING)
RSLV 06/05/2019 06/05/2019 09/06/2019
 
012 ( 53) GFCI HAS NOT BEEN PROVIDED
(GROUND FLOOR) GND 210.8 NOT PROVIDED GFCI EXAM ROOM.
RSLV 06/05/2019 06/05/2019 09/06/2019
 
013 (999) OTHER
(GROUND FLOOR)GND 314.20 JUNCTION BOX SET BACK COMBUSTIBLE MATERIAL ( RECEPTIONDESK, WAITING AREA) T-OUT
OPEN 06/05/2019 06/05/2019
 
014 (999) OTHER
(GROUND FLOOR)GND 422.52 DRINKING FOUNTAIN OUTLET MUST BE GFCI PROTECTED
RSLV 06/05/2019 06/05/2019 09/06/2019
 
015 (999) OTHER
(MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)MEZ 110.3 STAIR C , TOP OF STAIR. LUMINARIES COVER , HANGING OUT
RSLV 06/05/2019 06/05/2019 09/06/2019
 
016 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS) ART. 110.16 ARC FLASH LABELS MISSING THROUGHOUT.
OPEN 09/06/2019 09/06/2019
 
017 (999) OTHER
(ALL FLOORS)CONTRACTOR NEEDS TO FILE FOR ALL OF THE FEEDERS. OBSERVED 6 SETS600; 6 SETS 350, 2 SETS 4/0-4; 1 SET 3/0-4; 2 SETS 2/0; 4 SETS1/0-4; 4 SETS #2/4; AND 9 SETS #6/4.
OPEN 09/06/2019 09/06/2019
 
018 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(CELLAR)ART. 250.24 THE NEUTRAL IS NOT BONDED IN THE FIRE PUMP SWITCH.
OPEN 09/06/2019 09/06/2019
 
019 ( 53) GFCI HAS NOT BEEN PROVIDED
(CELLAR) ART. 210.8CR-22& LL SEC1#22 GFCI OUTLET NEEDED
OPEN 09/06/2019 09/06/2019