Electrical Application Details for App #: B435151
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 727 6 AVENUE BROOKLYN BIN: 3017673     Block: 900   Lot: 7
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 727 6TH AV Census Tract:   147 Health Area:  4700
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   F
BROOKLYN, NY 11215 Community Board:   307
DOB Cross Street(s):    22 STREET,    23 STREET
Status:   C - JOB IS SIGNED OFF 08/08/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/01/2017 9:57 AM
Application Entered:   10/01/2017 Job Start Date:   10/03/2017
Last Change:   08/08/2018 Job End Date:   10/06/2017
Appointment Status:   
Last Inspection By:   SERGIY MOTORIN       On     06/14/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009745 Licensee Name: LOUIS DEMICHELE
Firm: 002678 Firm Name: ALL AROUND ELECTRIC CORP.
Firm Phone: 347-987-3556  Firm Address: 168 49TH STREET BROOKLYN NY 11232 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $160.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROUTIE LENOX
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200 AMP.
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  3#2/0 WIRES
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 7 #4-Wire 0 #10-Wire 0
Existing Meters 7 + New Meters 7 - Removed Meters 7 = Total Meters 7

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/01/2017 Notice: C - CALL TO OFFICE 06/01/2018
Power Issued: 10/01/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:   PICKUP ALL EXISTING RISERS

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: B435151
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/21/2017 11/25/2017 OSZ V (25) (2)
INSPECTION COMMENTS: CORRECT OBJECTIONS/RE-INSPECTION REQUIRED B435151
 
(2) 12/07/2017 12/07/2017 OSZ V X (20) (1)
INSPECTION COMMENTS: CONTRACTOR MUST AMEND APP TO SHOW CORRECT SCOPE OF WORK FOR MISSING SERVICE PANELS AND RISERS.
 
(3) 06/01/2018 06/01/2018 SGY V X (30) (4)
INSPECTION COMMENTS: JOB IN PROGRESS. APPLICATION CORRECTED (#B00048792I1EL).
 
(4) 06/14/2018 06/14/2018 SGY C R (20) (0)
INSPECTION COMMENTS: OBJECTIONS (7) RESOLVED. INSPECTION ONLY FOR SERVICE EQUIPMENT. FEEDERS FOR SUBPANELS DONE BY OTHER.

OBJECTION FOR APPLICATION #: B435151
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(CELLAR)NO BONDING OF GROUND IN 200 AMP SERVICE SWITCH. ART 250.92(C)
RSLV 11/21/2017 11/21/2017 06/14/2018
 
002 (123) SERVICE DISCONNECTS ARE NOT PROPERLY GROUPED/LABELED
(CELLAR)NO LABELING PROVIDED FOR 200 AMP SERVICE SWITCH AND METERS. ART.230.72(A)
RSLV 11/21/2017 11/21/2017 06/14/2018
 
003 (279) WATER METER JUMPER IS MISSING/IMPROPER
(BASEMENT) WATER METER JUMPER NOT PROPERLY INSTALLED. ART. 250.53
RSLV 12/07/2017 12/07/2017 06/14/2018
 
004 (999) OTHER
(BASEMENT) (ART. 250.66) SIZE GROUND CONDUCTOR
RSLV 06/01/2018 06/01/2018 06/14/2018
 
005 (999) OTHER
(BASEMENT)(ART. 348.60) FMC WITHOUT EGC (AFTER PANELS, ALL SUBPANELS WITHOUTGROUND)
RSLV 06/01/2018 06/01/2018 06/14/2018
 
006 (999) OTHER
(BASEMENT) (ART. 250.2) SCREW FOR MIGB
RSLV 06/01/2018 06/01/2018 06/14/2018
 
007 (999) OTHER
(BASEMENT)(ART. 250.24(A)) NEUTRAL BONDED LOAD SIDE (ALL PANELS AFTER SS)
RSLV 06/01/2018 06/01/2018 06/14/2018