Electrical Application Details for App #: Z128087
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 525 WEST END AVENUE MANHATTAN BIN: 1033916     Block: 1247   Lot: 29
   
Application Completed and Certified

Filed: 525 W END AV Census Tract:   1710 Health Area:  3400
1H Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10024 Community Board:   107
DOB Cross Street(s):   WEST 85 STREET,    WEST 86 STREET
Status:   C - JOB IS SIGNED OFF 06/18/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/26/2010 9:44 AM
Application Entered:   10/26/2010 Job Start Date:   10/27/2010
Last Change:   06/18/2012 Job End Date:   09/12/2011
Appointment Status:   
Last Inspection By:   DIAMOND, R.       On     06/01/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011509 Licensee Name: MORGAN J TOREN
Firm: 002978 Firm Name: A.C. MORGAN ELECTRIC
Firm Phone: 718-549-6800  Firm Address: 3601 RIVERDALE AVENUE BRONX NY 10463 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $91.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: KAM SIEW
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  1- 4#2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  2- 100A
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  1H  25  28    10  25         
Buildings Total 25  28    10  25              
Total Units : 94 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/26/2010 Notice: 1 - FIRST NOTICE 04/09/2012
Power Issued: 10/26/2010 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: Z128087
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/31/2012 04/09/2012 DAH A G (30) (2) Y
INSPECTION COMMENTS: NONE
 
(2) 05/15/2012 05/31/2012 RDI J R E (65) (0) Y
INSPECTION COMMENTS: *CONTRACTOR TO CALL FOR RE-INSPECTION - COULD NOT SHUT OR TEST CIR- CUITS IN ACTIVE MEDICAL FACILITY. 1H & 1D COMBINED MED OFFICE.(NEW SEC ADDED TO MEDICAL OFFICE PROR TO 2011 CODE)VIOL DID NOT PERTAIN TO
 
(3) 06/01/2012 06/14/2012 RDI C E (70) (0) Y
INSPECTION COMMENTS: *NEW ADDITION TO DR.OFFICE(2H)002978

OBJECTION FOR APPLICATION #: Z128087
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
JUMPER NOT INSTALLED AT WATER METER
RSLV 03/31/2012 03/31/2012 05/15/2012
 
002 (999) OTHER
BSMT,SUPPLEMENTED GROUND NOT INSTALLED 250.50, NOT A FINAL INSPECTION
RSLV 03/31/2012 03/31/2012 05/15/2012