NYC Department of Buildings
Electrical Application Details for App #: Y156663
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 2455 GRAND AVENUE BRONX BIN: 2014636     Block: 3213   Lot: 40
   

DOB NOW: Inspections


Filed: 2455 GRAND AV Census Tract:   263 Health Area:  0320
BASEMENT Admin Area:   Y - BRONX Inspection Area:   F
BRONX, NY 10468 Community Board:   207
DOB Cross Street(s):   WEST FORDHAM ROAD,    WEST 188 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   P - PICK-UP eFiled:   NO
Application Entered:   07/25/2011 Job Start Date:  
Last Change:   08/22/2025 Job End Date:  
Appointment Status:   
Last Inspection By:   ALBERT HANSON       On     07/24/2011      
Field Disp:   W - ISSUE OBJECTION TO OWNER
Energize Recommendation:  
Objection Disposition:  

License #: Licensee Name: UNKNOWN
Firm: Firm Name: UNKNOWN
Firm Phone:   Firm Address:  

Work Started or Filed by Others: NO
Work Category:    Work To Be Done:   Total Fee:  $0.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: ELLEN MATZ
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 07/25/2011
Power Issued: Response:  

Follow-Up: V - OWNER OBJECTION 07/25/2011
Contractor's Comments:  WEST FORDHAM ROAD & WEST 188TH ST

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: Y156663
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/24/2011 07/25/2011 ATH W (45) (9)
INSPECTION COMMENTS: X

OBJECTION FOR APPLICATION #: Y156663
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
ALL DISCONNECT SWITCHES IN BASEMENT
OPEN 07/24/2011 07/24/2011
 
003 ( 19) DEFECTIVE WIRING IS IN USE
USING ALUMINUM FOIL ON FUSES
OPEN 07/24/2011 07/24/2011
 
004 ( 19) DEFECTIVE WIRING IS IN USE
CONDUCTORS NOT IN RACEWAY
OPEN 07/24/2011 07/24/2011
 
005 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
BASEMENT
OPEN 07/24/2011 07/24/2011
 
006 ( 29) OUTLET BOXES ARE NOT COVERED
TROUGH COVERS MISSING, DICONNECT COVERS, CEILING BOXES IN BASEMENT
OPEN 07/24/2011 07/24/2011
 
007 ( 41) LOCKNUTS ARE NOT MADE UP TIGHT
LOCKNUTS NOT TIGHT IN TROUGH
OPEN 07/24/2011 07/24/2011
 
008 (999) OTHER
SERVICE CONDUCTORS SPLICED IN BASEMENT 230.46
OPEN 07/24/2011 07/24/2011
 
009 (999) OTHER
NO NEUTRAL AT DISCONNECT SWITCH IN BASEMENT 250.24
OPEN 07/24/2011 07/24/2011
 
010 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
#12 WIRE FUSED AT 30 AMPS
OPEN 07/24/2011 07/24/2011