Electrical Application Details for App #: M333677
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 537 GREENWICH STREET MANHATTAN BIN: 1010367     Block: 597   Lot: 39
   
Application Completed and Certified

Filed: 545 GREENWICH ST Census Tract:   37 Health Area:  6800
1ST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10013 Community Board:   102
Special Place Name:   OTIS ELEVATOR SHOP
DOB Cross Street(s):   VANDAM STREET,    CHARLTON STREET
Status:   C - JOB IS SIGNED OFF 06/10/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/05/2012 4:05 PM
Application Entered:   11/05/2012 Job Start Date:   11/07/2012
Last Change:   06/10/2013 Job End Date:   12/07/2012
Appointment Status:   
Last Inspection By:   BINGEL, LORI       On     05/30/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011833 Licensee Name: PATRICK B GALLAGHER
Firm: 004148 Firm Name: 2G ELECTRICAL, INC
Firm Phone: 212-260-7920  Firm Address: 229 SULLIVAN STREET NEW YORK NY 10012 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $62.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   WORK SHOP
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JAMES MOREL
Owner Business Name: ARCHSTONE BUILDERS
Authorized Representative:  JAMES MOREL
Relationship To Owner:   GENERAL CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    30  28    30         
Buildings Total 30  28    30              
Total Units : 99 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/06/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  OTIS SHOP

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M333677
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/24/2013 05/06/2013 JKF A (60) (4) Y
INSPECTION COMMENTS: **SEE OBJECTIONS
 
(2) 05/30/2013 06/10/2013 LBI C R (20) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M333677
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
AIR CONDITIONER: TWO CONDUCTORS ON ONE GROUND LUG A/C COMPRESSORDISCONNECT
RSLV 04/24/2013 04/24/2013 05/30/2013
 
002 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
PANEL
RSLV 04/24/2013 04/24/2013 05/30/2013
 
003 ( 31) MORE THAN ALLOWABLE # OF CONDUCTORS ARE IN OUTLET BOX
CEILING: 4 11/16 BOXES - PANEL FEED TO WAREHOUSE LIGHTINGTWO BOXES AT CEILING
RSLV 04/24/2013 04/24/2013 05/30/2013
 
004 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
WAREHOUSE: CALES SECURED WITH PLASTIC WIRE TIES
RSLV 04/24/2013 04/24/2013 05/30/2013