Electrical Application Details for App #: M354082
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 502 CANAL STREET MANHATTAN BIN: 1083533     Block: 595   Lot: 40
   
Application Completed and Certified

Filed: 502 CANAL ST Census Tract:   39 Health Area:  7700
GROUND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   101
DOB Cross Street(s):   GREENWICH STREET,    WASHINGTON STREET
Status:   C - JOB IS SIGNED OFF 12/29/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/23/2014 2:45 PM
Application Entered:   05/23/2014 Job Start Date:   05/24/2014
Last Change:   12/29/2014 Job End Date:   05/25/2014
Appointment Status:   
Last Inspection By:   FENTY, WAYNE       On     12/22/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010836 Licensee Name: RICHARD SCIOLTO
Firm: 004239 Firm Name: QUEENS ELEC AND SOLAR INC
Firm Phone: 718-472-2145  Firm Address: 23-16 40TH AVENUE LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $175.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   PLP METER
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MICHAEL MARINO
Owner Business Name: MJM CONSTRUCTION
Authorized Representative:  RICHARD SCIOLTO
Relationship To Owner:   ELECTRICIAN


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  5  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    22  85    40  122         
Buildings Total 22  85    40  122              
Total Units : 273 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/23/2014 Notice: 1 - FIRST NOTICE 10/31/2014
Power Issued: 05/23/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  FILING FOR A PLP METER AND PANEL CIRCUITS

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M354082
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/28/2014 10/31/2014 EDB A E (60) (14) Y
INSPECTION COMMENTS: NONE
 
(2) 12/22/2014 12/29/2014 WYF C R E (35) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M354082
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (109) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
1FL: NO ACCESS TO GEC CONNECTION. 110.26
RSLV 10/28/2014 10/28/2014 12/22/2014
 
002 ( 19) DEFECTIVE WIRING IS IN USE
1FL: SERV ENTER CONDUCTORS IN HALLOW SPACE. AM.230.43
RSLV 10/28/2014 10/28/2014 12/22/2014
 
003 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
1FL: SERV.ENTER CONDUCTOR FOR FA S.S. UNDERSIZE. AM 230.31B
RSLV 10/28/2014 10/28/2014 12/22/2014
 
004 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
BSMT: WATER MAIN UNDER SIZE (2 X 4/0 ON #2 AWG) T.250.66
RSLV 10/28/2014 10/28/2014 12/22/2014
 
005 (999) OTHER
1ST FL: PLP PANEL MULTIWIRE CKT NO GROUPED,NO SIMULT TRIP. 210.4
RSLV 10/28/2014 10/28/2014 12/22/2014
 
006 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
1FL: EMT NOT PROPERLY SUPPORTED. 358.30
RSLV 10/28/2014 10/28/2014 12/22/2014
 
007 (311) FIXTURE NOT APPROVED FOR DAMP/WET LOCATION
2FL: BATHRM NOT APPROVED LIGHT FIXTURE. 410.10
RSLV 10/28/2014 10/28/2014 12/22/2014
 
008 (999) OTHER
2FL: CLOSET RECEPTACLE NOT FLUSH W/WOOD. 314.20,21
RSLV 10/28/2014 10/28/2014 12/22/2014
 
009 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
3FL: LAUNDRY RECEPTACLE NOT A.F.C.I. PROTECTED(110V) 210.12
RSLV 10/28/2014 10/28/2014 12/22/2014
 
010 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
2FL: OUTDOOR G.F.C.I.NOT WTR. 406.8A
RSLV 10/28/2014 10/28/2014 12/22/2014
 
011 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
2FL: OUTDOOR A/C UNIT NOT PROPERLY GND(LFMC). 250.112,118
RSLV 10/28/2014 10/28/2014 12/22/2014
 
012 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
1FL: KITCHEN LIGHTS ON SMALL APPLIANCE CKT. 210.52B2
RSLV 10/28/2014 10/28/2014 12/22/2014
 
013 (999) OTHER
1FL: KITCHEN ISLAND RECEPTACLE MORE THAN6" OVER HANG. 210.52C5X
RSLV 10/28/2014 10/28/2014 12/22/2014
 
014 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
FRONT: NO RECEPTACLE PROVIDED AT FRONT OF BUILDING UNIT. 210.52E
RSLV 10/28/2014 10/28/2014 12/22/2014