BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M244117
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 50 PINE STREET MANHATTAN BIN: 1001011     Block: 41   Lot: 7501
   
Application Completed and Certified

Filed: 50 PINE ST Census Tract:   7 Health Area:  7700
NONE Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10005 Community Board:   101
DOB Cross Street(s):   WILLIAM STREET,    PEARL STREET
Status:   C - JOB IS SIGNED OFF 09/01/2006
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   04/08/2005 Job Start Date:   03/25/2005
Last Change:   09/01/2006 Job End Date:   03/25/2006
Appointment Status:   
Last Inspection By:   HINDS EUGENE       On     05/08/2006      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  

License #: 010548 Licensee Name: ANTHONY REALE
Firm: 003631 Firm Name: AA REALE ELECTRIC INC
Firm Phone: 718-499-8731  Firm Address: 4223 1ST AVENUE BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,590.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: 50 PINE ST ASS LLC
Authorized Representative:  50 PINE ST ASS LLC
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  1  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  20  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  5  
D. Over 250 MCM  4  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  20  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 21 #4-Wire 4 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/08/2005 Notice:  
Power Issued: 04/08/2005 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M244117
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/08/2006 05/24/2006 EHD C (30) (0) Y
INSPECTION COMMENTS: NONE




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order