BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A300099
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 140-75 ASH AVENUE QUEENS BIN: 4539326     Block: 5182   Lot: 34
   
Application Completed and Certified

Filed: 140-75 ASH AV Census Tract:   857 Health Area:  1200
BASE.1.2.3.4.5..6.7.FL Admin Area:   A - QUEENS Inspection Area:   B
QUEENS, NY 11355 Community Board:   407
Related Job Number:    402510216
DOB Cross Street(s):   KISSENA BOULEVARD,    BOWNE STREET
Status:   C - JOB IS SIGNED OFF 04/29/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/11/2012 11:14 PM
Application Entered:   02/11/2012 Job Start Date:   02/13/2012
Last Change:   04/29/2013 Job End Date:   12/13/2012
Appointment Status:   
Last Inspection By:   BASDEO, C       On     04/23/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011509 Licensee Name: MORGAN J TOREN
Firm: 002978 Firm Name: A.C. MORGAN ELECTRIC
Firm Phone: 718-549-6800  Firm Address: 3601 RIVERDALE AVENUE BRONX NY 10463 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,624.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (8  Stores, 36 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GEORGE MAN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  
C. 201 Up to 600 AMPS  3  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  4  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  36  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    15                 
001    20  20  15               
002    20  20  15               
003    40  120  18  30               
004    40  120  18  30               
005    40  120  18  30               
006    40  120  18  30               
007    20  60  10  20               
Buildings Total 235  585  94  175                  
Total Units : 1089 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 36 #4-Wire 7 #10-Wire 2
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/11/2012 Notice: 1 - FIRST NOTICE 05/11/2012
Power Issued: 02/11/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: A300099
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/04/2012 05/11/2012 EBT V E (45) (5) Y
INSPECTION COMMENTS: VIOLATIONS
 
(2) 04/23/2013 04/29/2013 COB C R E (120) (0) Y
INSPECTION COMMENTS: CERTIFICATE

OBJECTION FOR APPLICATION #: A300099
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
ALL FLOORS SECURING ART 320.30 (A)(B) (C)
RSLV 05/04/2012 05/04/2012 04/23/2013
 
002 (999) OTHER
ALL FLOORS BONDING RADIUS ART 320.24
RSLV 05/04/2012 05/04/2012 04/23/2013
 
003 ( 32) MORE THAN ALLOWABLE # OF CONDUCTORS ARE IN JUNCTION BOX
ALL FLOORS WIRE COUNT IN SWITCH BOXES ART 314.16
RSLV 05/04/2012 05/04/2012 04/23/2013
 
004 (999) OTHER
ALL FLOORS PROTECT CABLES 1/16 IN STEEL CLOSER THAN 1/4 "300.4 A & D
RSLV 05/04/2012 05/04/2012 04/23/2013
 
005 (999) OTHER
ALL FLOORS MORE THEN 1/4" SET BACK ON BOXES 314.20
RSLV 05/04/2012 05/04/2012 04/23/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back