BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M327062
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 5 UNIVERSITY PLACE MANHATTAN BIN: 1080105     Block: 548   Lot: 4
   
Application Completed and Certified

Filed: 5 UNIVERSITY PL Census Tract:   59 Health Area:  5700
CELLAR-SUB CELLAR & PENTHOUSE Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
Special Place Name:   NYU WEINSTEIN HALL KITCHEN & DIN
DOB Cross Street(s):   WASHINGTON SQUARE NORTH,    WASHINGTON MEWS
Status:   C - JOB IS SIGNED OFF 03/20/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/11/2012 7:03 AM
Application Entered:   05/11/2012 Job Start Date:   05/11/2012
Last Change:   03/20/2013 Job End Date:   08/30/2012
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     01/16/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010763 Licensee Name: STEPHEN ROSTOWSKY
Firm: 002342 Firm Name: ROCKMOR ELEC. ENTERPR INC
Firm Phone: 718-633-3700  Firm Address: 1042 39TH STREET BROOKLYN NY 11219 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $954.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   RESIDENTIAL/ ASSEMBL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: NYU WEINSTEIN HALL
Authorized Representative:  JOHN PRENDERGAST
Relationship To Owner:   CONSTRUCTION MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  #2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  5  3/0
D. Over 250 MCM  2  500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  7  5-200AMP & 2 100AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SC1                 
CEL    198  86    28  190  35  136         
PEN                     
Buildings Total 200  89    30  191     136           
Total Units : 646 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/09/2012
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  #20364

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M327062
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/18/2012 11/09/2012 JVA A (110) (3) Y
INSPECTION COMMENTS: *SEE OBJECTIONS
 
(2) 01/16/2013 01/25/2013 TSO C R (50) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M327062
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
CEL: BARE #12 WIRE USED TI TIE BREAKER..... - 110.2
RSLV 10/18/2012 10/18/2012 01/16/2013
 
002 (229) SPLICE BOXES NOT ACCESSIBLE
CEL: ELEC CLOSET SPLICE BOX FOR ASCO SW.... - 314.29
RSLV 10/18/2012 10/18/2012 01/16/2013
 
003 (999) OTHER
CEL: MULTIWIRE BRANCH CKTS NOT ON SINGLE HANDLE BREAKER.. - 210.4B
RSLV 10/18/2012 10/18/2012 01/16/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back