BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M323108
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 163 WEST 10 STREET MANHATTAN BIN: 1010835     Block: 611   Lot: 32
   
Application Completed and Certified

Filed: 163 W 10 ST Census Tract:   73 Health Area:  6400
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   WAVERLY PLACE,    7 AVENUE SOUTH
Status:   C - JOB IS SIGNED OFF 10/27/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/27/2012 3:19 PM
Application Entered:   01/27/2012 Job Start Date:   01/27/2012
Last Change:   10/27/2014 Job End Date:   04/20/2012
Appointment Status:   
Last Inspection By:   SCHUSZTER, NORBET       On     10/22/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012359 Licensee Name: JOHN S KARALIS
Firm: 003811 Firm Name: TRIBORO ELEC'L CONTR'G CO
Firm Phone: 718-786-0913  Firm Address: 39-02 29TH STREET LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $600.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 16 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOE MENDLER
Owner Business Name: HMV REALTY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  200A
C. 201 Up to 600 AMPS  1  400A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  4  3/0
D. Over 250 MCM  2  500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                     
Total Units : 3 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 3 #10-Wire 0
Existing Meters 21 + New Meters 3 - Removed Meters 1 = Total Meters 23

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/27/2012 Notice: 1 - FIRST NOTICE 09/17/2014
Power Issued: 01/27/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M323108
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/11/2014 09/17/2014 EID A E (40) (2) Y
INSPECTION COMMENTS: THIS APP REPLACE OLD APP #M321748 SEE CORRECTIONS TO WORK DESCRIPTION
 
(2) 10/22/2014 10/27/2014 NRS C R E (20) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M323108
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: PLP PNL ALL CKTS NO SIMULTANEOUS TRIP. 210.4(B)
RSLV 09/11/2014 09/11/2014 10/22/2014
 
002 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
BSMT: 100A CKT BKR USED AS OCP IS NOT MAIN BKR IN PLP PNL
RSLV 09/11/2014 09/11/2014 10/22/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back