BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M318093
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 363 WEST 30 STREET MANHATTAN BIN: 1013511     Block: 754   Lot: 1
   
Application Completed and Certified

Filed: 363 W 30 ST Census Tract:   103 Health Area:  5500
BSMT Admin Area:   M - MANHATTAN Inspection Area:   Q
NEW YORK, NY 10001 Community Board:   104
DOB Cross Street(s):    8 AVENUE,    9 AVENUE
Status:   C - JOB IS SIGNED OFF 11/07/2011
Request Type:   P - PICK-UP eFiled:   YES
Application Entered:   09/23/2011 Job Start Date:   09/26/2011
Last Change:   11/07/2011 Job End Date:   10/15/2011
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     10/31/2011      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010275 Licensee Name: FRANK RAPPO
Firm: 001195 Firm Name: R & L SYSTEMS, INC.
Firm Phone: 718-397-5394  Firm Address: 37-20 56TH STREET WOODSIDE NY 11377 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $40.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LORI ZUCKER
Owner Business Name: KANGAROO REALITY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                       
Buildings Total                       
Total Units : 1 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  08/24/2011
Power Issued: Response: F - FILED TO REMOVE OBJECTION 09/23/2011

Follow-Up: X - FILED APPL,NOW CLOSED 09/23/2011
Contractor's Comments:  

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M318093
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/20/2011 08/24/2011 DAH W (45) (2)
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 10/31/2011 11/07/2011 GYM C R (35) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M318093
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
BRANCH CKT WIRING - 2- #12 AWG SINGLE CORECOMM: TWO SINGLE CORE #12 WIRES INSTALLED EXPOSED
RSLV 08/20/2011 08/20/2011 10/31/2011
 
002 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
1- 2"KO AT SIDE OF 42 CKT P.P*NOT A FINAL*
RSLV 08/20/2011 08/20/2011 10/31/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order