BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Applications  |  Elevators  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B372217
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 600 STERLING PLACE BROOKLYN BIN: 3029476     Block: 1175   Lot: 33
   
Application Completed and Certified

Filed: 600 STERLING PL Census Tract:   217 Health Area:  2720
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11238 Community Board:   308
DOB Cross Street(s):   CLASSON AVENUE,    FRANKLIN AVENUE SHUTTLE LINE
Status:   C - JOB IS SIGNED OFF 03/31/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/10/2013 3:27 PM
Application Entered:   09/10/2013 Job Start Date:   09/10/2013
Last Change:   03/31/2015 Job End Date:   03/10/2014
Appointment Status:   
Last Inspection By:   ROBINSON HEATH       On     03/26/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009791 Licensee Name: JOSEPH B JORDAN
Firm: 004329 Firm Name: GOTHAM WIRING LICENSED
Firm Phone: 718-295-6430  Firm Address: 649A EAST 183RD STREET ELECTRICAL CONTRACTORS IN BRONX NY 10458 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $188.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SOL STEINLAUF
Owner Business Name: S & Z REALTY
Authorized Representative:  JOSEPH JORDAN
Relationship To Owner:   CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 6 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/10/2013 Notice: 1 - FIRST NOTICE 12/23/2013
Power Issued: 09/10/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REPLACING BASEMENT SERVICE EQUIPMENT TO EXISTING APARTMENT RISERS

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: B372217
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/18/2013 12/23/2013 CLC V D (45) (5) Y
INSPECTION COMMENTS: N
 
(2) 03/12/2015 03/16/2015 CCH N (0) (0) Y
INSPECTION COMMENTS: NO ACCESS
 
(3) 03/26/2015 03/31/2015 HRB C R E (60) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B372217
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
200 AMP SVC SW NEUTRAL NOT BONDED 250.92
RSLV 12/18/2013 12/18/2013 03/26/2015
 
002 (999) OTHER
PLP PANEL NEUTRAL BONDED AFTER SVC SW 250.24 A5
RSLV 12/18/2013 12/18/2013 03/26/2015
 
003 (999) OTHER
SVC GND RACEWAY NOT CONTINOUS 250.64
RSLV 12/18/2013 12/18/2013 03/26/2015
 
004 (999) OTHER
SVC ENT RACEWAY NOT BONDED TO ENCLOSURES 250.92
RSLV 12/18/2013 12/18/2013 03/26/2015
 
005 ( 19) DEFECTIVE WIRING IS IN USE
SVC END BOX RUSTY AND DEFECTIVE
RSLV 12/18/2013 12/18/2013 03/26/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.