Electrical Application Details for App #: M396281
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 627 GREENWICH STREET MANHATTAN BIN: 1080188     Block: 602   Lot: 58
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 627 GREENWICH ST Census Tract:   69
CEL, ROF, 001-12 Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   LEROY STREET,    MORTON STREET
Status:   C - JOB IS SIGNED OFF 05/11/2022
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   05/18/2017 Job Start Date:   05/04/2017
Last Change:   05/11/2022 Job End Date:   03/04/2019
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     05/11/2022      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011399 Licensee Name: JEFF SKOWRONSKI
Firm: 002489 Firm Name: INTER CONNECTION ELETRIC
Firm Phone: 718-748-9800  Firm Address: 209 GRANITE AVE STATEN ISLAND NY 10303 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
Total Fee:  $5,040.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  122433937
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   54437     Submittal #: 16A0803  
Owner / Occup: SHAI SHAMIR
Owner Business Name: 90 MORTON OWNERS, LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  2-60A 120/208V
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  600A 120-208V FIRE PUMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  2  1600A, 2500A 120/208V
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  65  
B. Over #2 to 1/0  22  
C. Over 1/0 to 250 MCM  15  
D. Over 250 MCM  39  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  49  120/208V
D. 3 Phase Over 225 AMPS  4  120/208V
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    98  33    15  98  10  115         
001    131  103  43  131  38         
002    172  203  108  172  47         
003    172  193  108  172  47         
004    172  190  108  172  47         
005    172  187  108  172  47         
006    172  187  108  172  47         
007    172  189  108  172  47         
008    152  172  98  152  38         
009    116  153  63  116  38         
010    116  154  63  116  25         
011    66  129  51  66  12         
012    66  123  51  66  12         
ROF    38  13    14  38  22  388         
Buildings Total 1815  2029  35  1046  1815     948           
Total Units : 7688 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 36 #10-Wire 1
Existing Meters 0 + New Meters 38 - Removed Meters 0 = Total Meters 38

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/18/2017 Notice: 1 - FIRST NOTICE 05/10/2022
Power Issued: 05/18/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M396281
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/19/2022 02/20/2022 ASK V (377) (32)
INSPECTION COMMENTS: FAIL. INSPECTION IN COMPLETED. OBJECTION ISSUED. ATOI MARCIN . POOL AND SAUNA APP M00481361, APT 9A NEW APP M00253364, 11 PH A UNDER CONSTRUCTION NO NEW APP, 11 PH B NEW APP M00263018, APT 7A NEW APP M00480208. NO ACCESS TO THE THE 4 FLOOR T-OUT, 5A,5B NO ACCESS, 2A,2B NO ACCESS, 8 FLOOR NO ACCESS T-OUT . FULL INSPECTION AT RETURN.
 
(2) 05/02/2022 05/03/2022 SWR V Y (170) (10)
INSPECTION COMMENTS: INSPECTION INCOMPLETE. OBJECTION ISSUED. ATOI SINGH.. NO ACCESS TO THE 4 FLOOR T-OUT, 5A,5B NO ACCESS, 2A,2B NO ACCESS, T-OUT . FULL INSPECTION AT RETURN. SEE PREVIOUS INSPECTORS NOTES.
 
(3) 05/09/2022 05/10/2022 ASK V R (120) (3)
INSPECTION COMMENTS: FAIL. INSPECTION COMPLETED. OBJECTION ISSUED
 
(4) 05/11/2022 05/11/2022 TSO J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-22-000015204
 
(5) 05/11/2022 05/11/2022 TSO J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-22-000015205
 
(6) 05/11/2022 05/11/2022 TSO C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-22-000015206

OBJECTION FOR APPLICATION #: M396281
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 005) 5D APT PENDANT LIGHT NOT GROUNDED ART. 410.40
RSLV 02/19/2022 02/19/2022 05/02/2022
 
002 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 005) APT. 5D BOX NOT SUPPORTED T-OUT ART. 314.25
RSLV 02/19/2022 02/19/2022 05/02/2022
 
003 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 005) APT 5D OPEN SPLICES ,ART. 300.15
RSLV 02/19/2022 02/19/2022 05/02/2022
 
004 (145) APPLIANCE DISCONNECT NOT PROVIDED/IDENTIFIED.
(ALL FLOORS)KITCHEN APPLIANCES NO DISCONNECTS T-OUT ART.422.30, 422.31
RSLV 02/19/2022 02/19/2022 05/09/2022
 
005 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS)ALL AIR HANDLERS FUSED NOT AS PER MANUF. SPEC. 15 AMP MAX , FUSED 20AMP ART. 110.2
RSLV 02/19/2022 02/19/2022 05/02/2022
 
006 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS)NO ACCESS TO THE 8 FLOOR APTS. ,5B,5A, 4 FLOOR NO ACCESS TO THEAPTS. 2A,2B NO ACCESS.
RSLV 02/19/2022 02/19/2022 05/09/2022
 
007 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS) PANEL HANDLE TIES NOT PROVIDED T-OUT ART.210.4B
RSLV 02/19/2022 02/19/2022 05/02/2022
 
008 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS) ARC FLASH LABELS NOT PROVIDED ART, 110.16
RSLV 02/19/2022 02/19/2022 05/02/2022
 
009 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS) PANEL DIRECTORY MISSING T-OUT ART.408.4
RSLV 02/19/2022 02/19/2022 05/02/2022
 
010 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS) APT 11 PH A UNDER CONSTRUCTION
RSLV 02/19/2022 02/19/2022 05/02/2022
 
011 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS) GFCI NOT TR TYPE T-OUT ART. 406.11
RSLV 02/19/2022 02/19/2022 05/02/2022
 
012 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS) HEAT TRACE NOT GFPE PROTECTED, ART.427.22
RSLV 02/19/2022 02/19/2022 05/02/2022
 
013 (284) NO OUTLET FOR KITCHEN ISLAND
(ALL FLOORS) KITCHEN ISLAN GFCI LOCATION ART.210.52C2
RSLV 02/19/2022 02/19/2022 05/02/2022
 
014 ( 53) GFCI HAS NOT BEEN PROVIDED
(ALL FLOORS) KITCHEN ISLAND GFCI NOT PROVIDED T-OUT ART 210.8
RSLV 02/19/2022 02/19/2022 05/02/2022
 
015 ( 53) GFCI HAS NOT BEEN PROVIDED
(ALL FLOORS)MEDICINE CABINET OUTLET NOT GFCI PROTECTED T-OUT ART 210.8
RSLV 02/19/2022 02/19/2022 05/02/2022
 
016 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS)AFCI NOT PROVIDED FOR ALL LISTED AREAS T-OUT ART 210.12B
RSLV 02/19/2022 02/19/2022 05/02/2022
 
017 (999) OTHER
(ALL FLOORS)CONTRACTOR NEEDS TO OPEN NEW APP TO CORRECT QUANTITY OF SERCVICESWITCHES , HEATERS , MOTORS, ETC. AND CORRECT SCOPE OF WOR SAME APTRENOWATED UNDER NEW APPS BY DIFERENT CONTRACTORS.
RSLV 02/19/2022 02/19/2022 05/09/2022
 
018 (999) OTHER
(ALL FLOORS)AFFIDAVIT FOR ALL KITCHEN APPLIANCES ART.250.122 , 110.2, 314.25,320.15
RSLV 02/19/2022 02/19/2022 05/09/2022
 
019 (126) BASEMENT WATER MAIN GROUND NOT INSTALLED ON WATER MAIN
(CELLAR) WATER MAIN GROUND NOT INSTALLED ON WATER MAIN ART 250
RSLV 02/19/2022 02/19/2022 05/02/2022
 
020 (169) TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED
(CELLAR) CONSTRUCTION TEMP NOT REMOVED T-OUT ART. 590.3D
RSLV 02/19/2022 02/19/2022 05/02/2022
 
021 (192) CONDUCTORS ARE OVER FUSED AS PER TABLE 310.16
(CELLAR) APT 9 400 AMP DISCONNECT WIRES OVER FUSED . ART 310.16
RSLV 02/19/2022 02/19/2022 05/02/2022
 
022 (192) CONDUCTORS ARE OVER FUSED AS PER TABLE 310.16
(CELLAR) GARBAGE COMPACTOR WIRE OVER FUSED #12 ON 30 AMP ART. 310.16
RSLV 02/19/2022 02/19/2022 05/02/2022
 
023 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(CELLAR) GARBAGE COMPACTOR GROUND UNDER SIZED. ART. 250.122
RSLV 02/19/2022 02/19/2022 05/02/2022
 
024 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR) WATER POMP FUSE NOT AS PER AB DRAWING ART. AM 110.2B
RSLV 02/19/2022 02/19/2022 05/02/2022
 
025 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR) RDB WIRE SETS NOT AS PER AB DRAWINGS ART. AM 110.2B
RSLV 02/19/2022 02/19/2022 05/02/2022
 
026 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR) HDB SECTION 2 , NOT AS PER AB DRAWINGS ART. AM. 110.2B
RSLV 02/19/2022 02/19/2022 05/02/2022
 
027 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR) SS#4 FUSE NOT AS PER AB DRAWINGS. ART.AM 110.2B
RSLV 02/19/2022 02/19/2022 05/02/2022
 
028 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR)APT 9 400 AMP DISCONNECT FUSE NOT AS PER AB DRAWINGS ART. AM 110.2B
RSLV 02/19/2022 02/19/2022 05/02/2022
 
029 (229) SPLICE BOXES NOT ACCESSIBLE
(CELLAR)JOCKEY PUMP CONNECTION (CONTRACTOR CANT FIND CONNECTION ) ART.110.2 314.29
RSLV 02/19/2022 02/19/2022 05/02/2022
 
030 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ROOF)GENERATOR BREAKERS SIZE NOT AS PER AB DRAWINGS ART.AM 110.2B
RSLV 02/19/2022 02/19/2022 05/02/2022
 
031 (307) NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT
(ROOF) ROOF OUTLET REQUIRED HVAC EQUIPMENT ART. 210.63
RSLV 02/19/2022 02/19/2022 05/02/2022
 
032 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ROOF) ROOF ATS ROOM EMT NOT SUPPORTED. ART. 358.30
RSLV 02/19/2022 02/19/2022 05/02/2022
 
033 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
(FLOOR: 005) DEFECTIVE LIGHT FIXTURE IS IN USE. 110.2 A
RSLV 05/02/2022 05/02/2022 05/09/2022
 
034 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
(FLOOR: 008)APT 8 D FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD KITCHEN.400.8
RSLV 05/02/2022 05/02/2022 05/09/2022
 
035 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 008)APT 8 D 8 A 8 B, DRYER OUTLET GROUND UNDERSIZED T-OUT. 250.122
RSLV 05/02/2022 05/02/2022 05/09/2022
 
036 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 008)APT 8 D, FLEXIBLE CORDS MAY BE USED FOR CONNECTION OF APPLIANCESIDENTIFIED HOOD DISCONNECT. 400.7 8
RSLV 05/02/2022 05/02/2022 05/09/2022
 
037 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 008)BOX SET BACK MORE THAN INTO COMBUSTIBLE MATERIAL. ART 314.20
RSLV 05/02/2022 05/02/2022 05/09/2022
 
038 ( 29) OUTLET BOXES ARE NOT COVERED
(FLOOR: 008) APT 8 D, SPLICE BOX OPEN IN KITCHEN CABINET. 314.25
RSLV 05/02/2022 05/02/2022 05/09/2022
 
039 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 008)APT 8 A, B AFCI PROTECTION NOT PROVIDED IN ALL AREAS LISTED T-OUT.210.12 B
RSLV 05/02/2022 05/02/2022 05/09/2022
 
040 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 008) AFCI PROTECTION NOT PROVIDED IN LISTED AREAS. 210.12
RSLV 05/02/2022 05/02/2022 05/09/2022
 
041 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS)STEAM UNIT DISCONNECT NOT LABEL / MARKED ABOVE CEILING T-OUT. 110.22
RSLV 05/02/2022 05/02/2022 05/09/2022
 
042 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS)NO MANUFACTURER LABEL AND LISTING FOR STEAM UNIT ABOVE CEILING /EQUIPMENT. 110.2
RSLV 05/02/2022 05/02/2022 05/09/2022
 
043 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 005) APT 5D HALLWAY OUTLET NOT WORKING ART.110.2
RSLV 05/09/2022 05/09/2022 05/11/2022
 
044 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 011)APT 11A KITCHEN ISLAND OUTLETS NOT GFCI PROTECTED ART.210.8
RSLV 05/09/2022 05/09/2022 05/11/2022
 
045 (999) OTHER
(ALL FLOORS)AFFIDAVIT FOR ALL KITCHEN APPLIANCES NO ACCESS TO THE WIRING T-OUTART.250.122, 314.25, 320.40, 422.30, 300.15,110.2
RSLV 05/09/2022 05/09/2022 05/11/2022