BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B215517
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 961 OCEAN AVENUE BROOKLYN BIN: 3120264     Block: 5206   Lot: 62
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 961 OCEAN AV Census Tract:   516 Health Area:  7210
067438 NONE Admin Area:   B - BROOKLYN Inspection Area:   K
BROOKLYN, NY 11226 Community Board:   314
DOB Cross Street(s):   DITMAS AVENUE,    NEWKIRK AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   07/11/2001 Job Start Date:   07/05/2001
Last Change:   08/22/2025 Job End Date:   07/30/2001
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   WONG, K.       On     02/15/2002      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  

License #: 011013 Licensee Name: VITO LOPA
Firm: 002351 Firm Name: HIGH BEAM ELECTRIC CORP.
Firm Phone: 718-477-2050  Firm Address: 443 WILD AVENUE STATEN ISLAND NY 10314 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
7 - HVAC WIRING
Total Fee:  $85.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Other
Store / Other:   CHURCH
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: PILGRAM WESLEYAN CHURCH
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                       
Total Units : 8 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 07/11/2001 Notice: 1 - FIRST NOTICE 02/22/2002
Power Issued: 07/11/2001 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: B215517
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/09/2002 01/14/2002 IJ1 I (30) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(2) 02/15/2002 02/22/2002 KIW V G (60) (2) Y
INSPECTION COMMENTS: No Inspection Comments For This Application




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back