BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M374748
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 56 LEONARD STREET MANHATTAN BIN: 1088646     Block: 176   Lot: 26
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 56 LEONARD ST Census Tract:   33 Health Area:  7700
ALL FLOORS SERVED, MR Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   101
Related Job Number:    104799648
DOB Cross Street(s):   WEST BROADWAY,    CHURCH STREET
Status:   C - JOB IS SIGNED OFF 11/12/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/11/2015 6:52 PM
Application Entered:   11/11/2015 Job Start Date:   12/01/2015
Last Change:   11/12/2019 Job End Date:   12/01/2018
Appointment Status:   
Last Inspection By:   RIVERA, F       On     11/12/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011986 Licensee Name: ANTHONY LUCIANO
Firm: 003652 Firm Name: JAM ELECTRICAL CORP
Firm Phone: 212-265-0142  Firm Address: 1133 6TH AVE 28TH FLOOR NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: KEYVAN KAZEMI
Owner Business Name: ALEXICO GROUP LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  ELEVATOR
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/18/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M374748
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/13/2019 07/13/2019 CDX V (60) (5)
INSPECTION COMMENTS: FAIL. SUPER OF BUILDING PRESENT ON INSPECTION. ELEVATOR 1P48938.
 
(2) 10/17/2019 10/18/2019 TOR V R (30) (1)
INSPECTION COMMENTS: FAIL
 
(3) 11/12/2019 11/12/2019 FRI C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000026235

OBJECTION FOR APPLICATION #: M374748
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
(GROUND FLOOR)GND 320.30 ARMORED CABLE ARE NOT PROPERLY SECURED. ( ELEVATOR ROOMC1)
RSLV 07/13/2019 07/13/2019 10/17/2019
 
002 (329) OPENINGS TO BE SEALED
(GROUND FLOOR) GND OPENINGS ARE NOT SEALED ( ELEVATOR ROOM C1)
RSLV 07/13/2019 07/13/2019 10/17/2019
 
003 (999) OTHER
(GROUND FLOOR)GND 620.53. LIGHT CAB DISCONNECT NOT PROVIDED WITH A SIGN TOIDENTIFY THE LOCATION OF THE SUPPLY SIDE OCPD ( ELEVATOR ROOM C1)ELEVATOR 1P48938
RSLV 07/13/2019 07/13/2019 10/17/2019
 
004 (999) OTHER
(GROUND FLOOR) PIT AND TOP OF CAB NEEDS FULL INSPECTION ( NO ACCESS)
RSLV 07/13/2019 07/13/2019 10/17/2019
 
005 (999) OTHER
(GROUND FLOOR)LIGHT CAB AND MOTOR DISCONNECTS , NEEDS FULL INSPECTION ( NO ACCESS)ELEVATOR 1P48938
RSLV 07/13/2019 07/13/2019 10/17/2019
 
006 (101) CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED
(ALL FLOORS) MOTORS NOT LISTED
RSLV 10/17/2019 10/17/2019 11/12/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order