BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M360261
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 2 BEDFORD STREET MANHATTAN BIN: 1008342     Block: 527   Lot: 1
   
Application Completed and Certified

Filed: 2 BEDFORD ST Census Tract:   67 Health Area:  6400
1-2 FLOORS Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   AVENUE OF THE AMERICAS,    DOWNING STREET
Status:   C - JOB IS SIGNED OFF 06/02/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/29/2014 9:22 AM
Application Entered:   10/29/2014 Job Start Date:   10/29/2014
Last Change:   06/02/2015 Job End Date:   12/22/2014
Appointment Status:   
Last Inspection By:   ELLIS DAVID       On     05/28/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010523 Licensee Name: VINCENT VERDEROSA
Firm: 001698 Firm Name: SUPER CHARGED ELEC. INC.
Firm Phone: 718-981-7173  Firm Address: 2 DUBOIS AVENUE STATEN ISLAND NY 10310 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $98.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MR CALABRIA
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  #3
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  #1  21  18    13  21         
002  #1  10  17  10             
Buildings Total 31  35  21  31              
Total Units : 123 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/14/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  PANEL, RISER, GENERAL WIRING

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M360261
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/09/2015 04/14/2015 NRS V (55) (7) Y
INSPECTION COMMENTS: DRYER RECE.E.B.J.NOT INSPECTED
 
(2) 05/28/2015 06/02/2015 EID C R (25) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M360261
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
1FL: REFRIDGE RECE HANGING ON CONDUCTORS,STOVE ALSO
RSLV 04/09/2015 04/09/2015 05/28/2015
 
002 (999) OTHER
1FL: 1 KITCHEN COUNTER CIRCUIT.. 210.52(B)(1)
RSLV 04/09/2015 04/09/2015 05/28/2015
 
003 (999) OTHER
2FL: NO RECE IN HALLWAY.. 210.52(H)
RSLV 04/09/2015 04/09/2015 05/28/2015
 
004 (999) OTHER
1FL: BACK YARD G.F.C.I.. 406.8
RSLV 04/09/2015 04/09/2015 05/28/2015
 
005 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
BASE: IN BASEMENT PANEL FEEDING APT.PANEL,DRYER,ETC
RSLV 04/09/2015 04/09/2015 05/28/2015
 
006 (999) OTHER
1FL: LFNC IN USE.. AM 356.102FL
RSLV 04/09/2015 04/09/2015 05/28/2015
 
007 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
1FL: REFR.& STOVE REC
RSLV 04/09/2015 04/09/2015 05/28/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back