NYC Department of Buildings
Electrical Application Details for App #: M282824
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 245 WEST 25 STREET MANHATTAN BIN: 1014198     Block: 775   Lot: 9
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 245 W 25 ST Census Tract:   91 Health Area:  5200
BASEMENT AND APT 1I, 1H Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   104
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 08/30/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/14/2008 2:06 PM
Application Entered:   07/14/2008 Job Start Date:   07/21/2008
Last Change:   08/30/2016 Job End Date:   07/19/2009
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     06/28/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  R - REMOVED

License #: 011538 Licensee Name: NICHOLAS BLASONE
Firm: 003044 Firm Name: NEW CENTURY ELEC'L CONTR
Firm Phone: 718-441-7123  Firm Address: 105-15 JAMAICA AVE INC. QUEENS NY 11418 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $124.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JAY HERNANDEZ
Owner Business Name: EJAM REALTY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  1 SET # 2 CONDUCTOR
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  2-1 PHASE 20-1 POLE BRKRS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 20  100  20  20                
Total Units : 168 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/14/2008 Notice: 1 - FIRST NOTICE 04/02/2009
Power Issued: 07/14/2008 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW METER FOR APT. 1I

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M282824
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/25/2009 04/02/2009 CLC A G (60) (8) Y
INSPECTION COMMENTS: NONE
 
(2) 06/28/2016 06/28/2016 BMP C R (20) (0)
INSPECTION COMMENTS: EQUIPMENT REMOVED. BUILDING RENOVATED. OBJECTIONS REMOVED. CERTIFIED.

OBJECTION FOR APPLICATION #: M282824
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
(ALL FLOORS) APTS. 1I,1H,BEDROOMS,OUTLETS WIRING DEFECTIVE
RSLV 03/25/2009 03/25/2009 06/28/2016
 
002 ( 19) DEFECTIVE WIRING IS IN USE
(ALL FLOORS) APTS.1I,1H BATHS GFCI WIRING DEVECTIVE
RSLV 03/25/2009 03/25/2009 06/28/2016
 
003 ( 19) DEFECTIVE WIRING IS IN USE
(ALL FLOORS) APTS.L 1I KITCHEN COUNTER GFCI WIRING DEFECTIVE
RSLV 03/25/2009 03/25/2009 06/28/2016
 
004 ( 6) FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION
(ALL FLOORS) APT. 1I NEED LOAD CALCULATION FOR FEEDER #6
RSLV 03/25/2009 03/25/2009 06/28/2016
 
005 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ALL FLOORS) APT. 1I PANEL 10 WIRE FUSED AT 50AMPS
RSLV 03/25/2009 03/25/2009 06/28/2016
 
006 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS) APT.1I FEEDER RACEWAY BEHIND STOVE IMPROPER CONN
RSLV 03/25/2009 03/25/2009 06/28/2016
 
007 (999) OTHER
(ALL FLOORS) APT 1H PANEL PHASE LEGS NOT BALANCED
RSLV 03/25/2009 03/25/2009 06/28/2016
 
008 ( 11) FEEDER CONDUCTORS ARE NOT OF PROPER SIZE
(ALL FLOORS) APT 1H#6 FEEDER IMPROPER SIZE
RSLV 03/25/2009 03/25/2009 06/28/2016