BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M352249
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 484 10 AVENUE MANHATTAN BIN: 1088764     Block: 735   Lot: 6
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 455 W 37 ST Census Tract:   111 Health Area:  5500
GROUND FLOOR STORE #1 Admin Area:   M - MANHATTAN Inspection Area:   Q
NEW YORK, NY 10018 Community Board:   104
DOB Cross Street(s):   DYER AVENUE,    10 AVENUE
Status:   C - JOB IS SIGNED OFF 05/03/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/04/2014 5:05 PM
Application Entered:   04/04/2014 Job Start Date:   04/04/2014
Last Change:   05/03/2016 Job End Date:   04/04/2015
Appointment Status:   
Last Inspection By:   MODELFINO, CARL C       On     04/08/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010190 Licensee Name: ABE HIMELFARB
Firm: 002663 Firm Name: ALEF ELEC'L CONTR'G INC
Firm Phone: 212-764-2200  Firm Address: 247 WEST 38TH STREET NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $176.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   BOXING GYM
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MICHAEL TOSTO
Owner Business Name: TITLE BOXING CLUB
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  EXISTING RISER
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    44  30    10  60      12     
Buildings Total 44  30    10  60          12      
Total Units : 156 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/08/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  EXISTING FEEDER BY OTHERS, WATER HEATER, EXISTING A/C, THREE EXIT LIGHTS, 48 FEET OF LIGHT TRCK

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M352249
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/26/2015 06/01/2015 UMS N (25) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW,NO ANSWER
 
(2) 07/02/2015 07/08/2015 GYM A (50) (3) Y
INSPECTION COMMENTS: 1- 225 AMP,1- 125 AMP 3PH PANELS
 
(3) 10/01/2015 10/08/2015 NRS N (10) (0) Y
INSPECTION COMMENTS: CONTRACTOR CANCELED INSPECTION NO SHOW
 
(4) 04/08/2016 04/13/2016 MLF C R (15) (0)
INSPECTION COMMENTS: ALL OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: M352249
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ALL FLOORS) 1ST FL: NEW 225 AMPS FUSE AT 400 AMPS
RSLV 07/02/2015 07/02/2015 04/08/2016
 
002 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ALL FLOORS) 1ST FL: NEW 225 AMP 500 MCM FEEDER LUGS
RSLV 07/02/2015 07/02/2015 04/08/2016
 
003 (999) OTHER
(ALL FLOORS)1ST FL: NO GROUPING HANDLE TIES FOR MUKTIWIRES CKTS.. ART 210.4(NEW BUILDING)
RSLV 07/02/2015 07/02/2015 04/08/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.