BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z162737
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 310 WEST 109 STREET MANHATTAN BIN: 1057310     Block: 1893   Lot: 24
   

DOB NOW: Inspections


Filed: 310 W 109ST Census Tract:   195 Health Area:  2310
5 STORY BUILDING Admin Area:   Z - UPPER MANHATTAN Inspection Area:   C
NEW YORK, NY 10025 Community Board:   107
Related Job Number:    121193332
DOB Cross Street(s):   BROADWAY,    RIVERSIDE DRIVE
Status:   K - CLOSED/CANCELLED 10/22/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/19/2017 3:57 PM
Application Entered:   09/19/2017 Job Start Date:   09/20/2017
Last Change:   10/22/2019 Job End Date:   12/31/2018
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     10/22/2019      
Field Disp:   K - OK TO CANCEL
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012602 Licensee Name: JACK FRANCOVIGLIA
Firm: 004438 Firm Name: J & F ELECL CONTNG INC
Firm Phone: 718-745-0300  Firm Address: 7618 13TH AVENUE, FL BSM ST 5 BROOKLYN NY 11228 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $450.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOSEPH ANNUNZIATA
Owner Business Name: OWNER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  3 PHASE 400AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  1 SETT 4 WIRE 500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  10  MAIN LUG SPH 20 BRKT
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  200AMP 3PH MAIN BRKT
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  1F  20  25  16               
001  1R  20  25  16               
Buildings Total 40  50  32                  
Total Units : 130 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 10 #4-Wire 1 #10-Wire 0
Existing Meters 10 + New Meters 11 - Removed Meters 10 = Total Meters 11

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/19/2017 Notice: 1 - FIRST NOTICE 06/06/2019
Power Issued: 09/19/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WIRING IN FIRST FLOOR

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: Z162737
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/30/2019 05/01/2019 CBK J (40) (0) Y
INSPECTION COMMENTS: CONTRACTOR NEED TO FILE NEW APP. WORK DONE ALL 10 APARTMENTS, STOVES, HEATERS AND 2 -100A HOT WATER TANKS. FULL INSPECTION NEEDED.
 
(2) 06/05/2019 06/06/2019 GYM V (75) (5)
INSPECTION COMMENTS: SEE APP # M00166479
 
(3) 10/22/2019 10/22/2019 DNM K R (15) (0)
INSPECTION COMMENTS: OK TO CANCEL IN REFERENCE TO APPLICATION# M00244421

OBJECTION FOR APPLICATION #: Z162737
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(FLOOR: 004) NEW BREAKER ELECTRIC RANGE
RSLV 06/05/2019 06/05/2019 10/22/2019
 
002 (999) OTHER
(ALL FLOORS) OUTLET BONES NOT BONDED 250.146
RSLV 06/05/2019 06/05/2019 10/22/2019
 
003 (999) OTHER
(BASEMENT) 600 AMP SERVICE SW. DOOR MUST BE OPEN AT LEAST 90 110.26
RSLV 06/05/2019 06/05/2019 10/22/2019
 
004 (999) OTHER
(BASEMENT) FIRE STOP REQUIRED CONDUITS 300.21
RSLV 06/05/2019 06/05/2019 10/22/2019
 
005 (999) OTHER
(BASEMENT)PAA REQUIRED OBSERVED 4, SETS 350 SERVICE& FEEDERS CONDUCTORS, NEEDTO ADDED MORE LIGHTS, SWITCHES, RECEPTACLES, APTS. # 1, # 2 PUBLICHALLWAYS.
RSLV 06/05/2019 06/05/2019 10/22/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order