BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M315151
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 335 WEST 18 STREET MANHATTAN BIN: 1013096     Block: 742   Lot: 7
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 351 W 18 ST Census Tract:   89 Health Area:  5600
7 TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10011 Community Board:   104
Special Place Name:   PS M440 SCHOOL
DOB Cross Street(s):    8 AVENUE,    9 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/02/2011 4:28 PM
Application Entered:   06/02/2011 Job Start Date:   06/02/2011
Last Change:   08/22/2025 Job End Date:   08/28/2011
Appointment Status:   
Last Inspection By:   DOYLEY, DEXTER       On     02/20/2014      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 010189 Licensee Name: ERIC P VITALE
Firm: 000695 Firm Name: INTERPHASE ELECTRIC CORP.
Firm Phone: 718-499-4121  Firm Address: 41 FALTBUSH AVENUE FLR 2 BROOKLYN NY 11217 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $912.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: NYC DEPT OF EDUCATION
Authorized Representative:  BRAREN VOLKERT
Relationship To Owner:   718-610-0334


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1   400 AMP 3 PH 4 W
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  3  2-SET O4 # 2 & 1 # 8
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  3  4 # 600 MCM & 1# 2/0 GRD.
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  4  2-100 A 2-225A 4WIRE
D. 3 Phase Over 225 AMPS  2  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
007    35  145  50  174  17         
Buildings Total 35  145  50  174              
Total Units : 421 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 03/05/2014
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  RENOVATION OF 7TH FL WEST 19 STREET SIDE, NEW 400 AMP FEEDERS, NEW PANELS,LIGHTING, POWER OUTLETS,CLOCK SYSTEM, PA ,TEL/DATA

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M315151
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/17/2012 08/04/2012 CCH V (90) (4) Y
INSPECTION COMMENTS: NONE
 
(2) 03/22/2013 04/01/2013 MFF N (20) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 04/30/2013 05/09/2013 IOS A Y (35) (1) Y
INSPECTION COMMENTS: NONE
 
(4) 02/20/2014 03/05/2014 DEX V Y (45) (4) Y
INSPECTION COMMENTS: OVER 2750 KVA

OBJECTION FOR APPLICATION #: M315151
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
400A SW GREEN WIRE TO NEUTRAL BAR 250.24A.5
RSLV 07/17/2012 04/30/2013 02/20/2014
 
002 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
KO MISSING TOP 400A SW
RSLV 07/17/2012 07/17/2012 04/30/2013
 
003 (999) OTHER
NEED LOAD CALCULATION FOR 2 SWITCH FEEDERS PANEL 220.11
RSLV 07/17/2012 07/17/2012 04/30/2013
 
004 ( 6) FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION
FEEDER DIAGRAM FOR INSPECTION 1-LINE
RSLV 07/17/2012 04/30/2013 02/20/2014
 
005 (999) OTHER
MORE THAN ONE SERVICE SWITCH TAPPED ON BUS BAR OF ENDLINE BOX- 230.40
RSLV 04/30/2013 04/30/2013 02/20/2014
 
006 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
NO ADVISORY BOARD APPROVAL
OPEN 02/20/2014 02/20/2014
 
007 (129) SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
OPEN 02/20/2014 02/20/2014
 
008 (133) NO GROUND ROD: BASEMENT OR OUTSIDE
NO GROUND ROD INSTALLED FOR NEW SERVICE SWITCH
OPEN 02/20/2014 02/20/2014
 
009 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
NO LABEL FOR SERVICE SWITCH
OPEN 02/20/2014 02/20/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back