BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M286763
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 151 EAST 81 STREET MANHATTAN BIN: 1047564     Block: 1510   Lot: 25
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 151 E 81ST ST. Census Tract:   140 Health Area:  3600
MOTOR ROOM Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10028 Community Board:   108
DOB Cross Street(s):   LEXINGTON AVENUE,    3 AVENUE
Status:   C - JOB IS SIGNED OFF 11/16/2023 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/07/2008 12:02 PM
Application Entered:   11/07/2008 Job Start Date:   12/08/2008
Last Change:   11/16/2023 Job End Date:   07/08/2009
Appointment Status:   
Last Inspection By:   ADAM ADAMSKI       On     05/30/2023      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011165 Licensee Name: JAMES KRUGER
Firm: 002557 Firm Name: VINTAGE ELEC. SERVICE INC
Firm Phone: 718-338-3910  Firm Address: 2812 HARWAY AVE BROOKLYN NY 11214 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: HPC GRAT REALTY
Authorized Representative:  STEPHEN RUOCCO
Relationship To Owner:   EXPEDITOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  7 STORIES
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 11/05/2021
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  #1144 NEW CONTROLLER AND SHAFT WIRING FOR 1P7763

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M286763
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/08/2020 12/09/2020 STP N (20) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(2) 08/23/2021 08/23/2021 EDB N (35) (0) Y
INSPECTION COMMENTS: DEV. # 1P7763. CALL CONTRACTOR, ANSWER MACHINE. NO SHOW, AS DIRECTED FROM OFFICE. INSPECTION INCOMPLETE.
 
(3) 08/27/2021 08/30/2021 SWR V (65) (3)
INSPECTION COMMENTS: INSPECTION COMPLETE. OBJECTIONS ISSUED.
 
(4) 11/05/2021 11/05/2021 PHG V X (20) (1)
INSPECTION COMMENTS: OBJECTIONS NOT FIXED
 
(5) 05/30/2023 05/30/2023 ASK C R (1) (0)
INSPECTION COMMENTS: PASS. INSPECTION COMPLETE. NEW APP M00846193

OBJECTION FOR APPLICATION #: M286763
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT) COLOR CODE FOR CONDUCTOR MAIN LINE DISCONNECT. ART 200.6
RSLV 08/27/2021 08/27/2021 05/30/2023
 
002 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT)CAR LIGHT DISCONNECT SWITCH MECHANICAL ROOM OCPD NOT PROVIDED WITHSIGN TO IDENTIFY TO THE LOCATION OF SUPPLY SIDE. 620.53
RSLV 08/27/2021 08/27/2021 05/30/2023
 
003 (220) DOUBLE LUGGING IN SERVICE SWITCH
(BASEMENT) DOUBLE LUGGING AT MAIN LINE DISCONNECT. 110.14 A
RSLV 08/27/2021 08/27/2021 05/30/2023
 
004 ( 19) DEFECTIVE WIRING IS IN USE
(BASEMENT) 14 WIRE USED FOR CAR LIGHTS 210.19
RSLV 11/05/2021 11/05/2021 05/30/2023



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order