BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Plumb. Inspections  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B310195
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 1322 AVENUE U BROOKLYN BIN: 3199489     Block: 7346   Lot: 9
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 1322 AV U Census Tract:   582 Health Area:  8710
BSMT,1ST FL Admin Area:   B - BROOKLYN Inspection Area:   P
BROOKLYN, NY 11229 Community Board:   315
DOB Cross Street(s):   EAST 13 STREET,    EAST 14 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/27/2008 4:04 PM
Application Entered:   10/27/2008 Job Start Date:   10/27/2008
Last Change:   08/22/2025 Job End Date:   06/30/2009
Appointment Status:   
Last Inspection By:   COHN, MARTIN       On     01/11/2012      
Field Disp:   N - NO ACCESS
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  X - NOT REMOVED

License #: 011737 Licensee Name: CHRISTOPHER BISHUNDAT
Firm: 003239 Firm Name: NEW GRAND ELECTRIC, INC.
Firm Phone: 212-219-4033  Firm Address: 71-73 ALLEN STREET NEW YORK NY 10002 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $184.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Other
Store / Other:   BANK
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LEE SOON
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  COMBONATION
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                 
001    100  50    30               
Buildings Total 102  52    31                
Total Units : 187 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 10/27/2008 Notice: C - CALL TO OFFICE 11/04/2009
Power Issued: 10/27/2008 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: B310195
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/04/2009 02/09/2009 PGR V E (50) (3) Y
INSPECTION COMMENTS: N
 
(2) 08/10/2009 08/19/2009 MC2 H X (60) (0) Y
INSPECTION COMMENTS: VIOLATION STILL REMAIN PLUS NEW P/U W 3
 
(3) 08/10/2009 08/19/2009 MC2 H X (60) (0) Y
INSPECTION COMMENTS: N
 
(4) 08/10/2009 08/19/2009 MC2 H X (60) (0) Y
INSPECTION COMMENTS: VIOLATIONS STILL REMAIN PLUS NEW P/U W 3
 
(5) 08/10/2009 08/19/2009 MC2 H X (60) (0) Y
INSPECTION COMMENTS: N
 
(6) 08/10/2009 08/19/2009 MC2 A R E (60) (6) Y
INSPECTION COMMENTS: VIOLATIONS STILL REMAIN PLUS NEW - P/U W3
 
(7) 10/26/2009 11/04/2009 JMZ H X (45) (0) Y
INSPECTION COMMENTS: N
 
(8) 01/11/2012 01/17/2012 MC2 N (30) (0) Y
INSPECTION COMMENTS: NO SHOW

OBJECTION FOR APPLICATION #: B310195
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ENTIRE OUTLET IN BANK
RSLV 02/04/2009 08/10/2009 08/10/2009
 
002 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
BSMT CONNECTOR IN WIREWAY
RSLV 02/04/2009 08/10/2009 08/10/2009
 
003 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BSMT SER ENT RACEWAY
RSLV 02/04/2009 08/10/2009 08/10/2009
 
004 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BASMT/SERVICE GROUND NOT PROPERLY TERMINATED IN LUG AT WATER MAIN
OPEN 08/10/2009 10/26/2009
 
005 ( 19) DEFECTIVE WIRING IS IN USE
ENTIRE/RECEPT OUTLETS THRU-OUT WIRES TO DEVICES NOT PROPERLY TERMINATED
OPEN 08/10/2009 10/26/2009
 
006 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
ENTIRE/RECEPT OUTLETS WHITE WIRE USED FOR GROUND, GREEN WIRE NOTPROVIDED
OPEN 08/10/2009 10/26/2009
 
007 ( 53) GFCI HAS NOT BEEN PROVIDED
BASEMENT/RECEPT OUTLET AT SERVICE EQUIPMENT NOT GFIC PROTECTED
OPEN 08/10/2009 10/26/2009
 
008 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BASEMENT/RECEPT OUTLET NOT BONDED TO BOX
OPEN 08/10/2009 10/26/2009
 
009 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BASEMENT/BONDING IN S/S LUG, SMALL STRANDS NOT PROPERLY TERMINATED
OPEN 08/10/2009 10/26/2009