BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M355595
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 238 EAST 33 STREET MANHATTAN BIN: 1078802     Block: 913   Lot: 44
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 238 E 33 ST Census Tract:   70 Health Area:  5800
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   N
NEW YORK, NY 10016 Community Board:   106
DOB Cross Street(s):    3 AVENUE,    2 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/01/2014 12:31 PM
Application Entered:   07/01/2014 Job Start Date:   07/01/2014
Last Change:   08/22/2025 Job End Date:   09/30/2014
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     12/14/2017      
Field Disp:   J - JOB IN PROGRESS
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  X - NOT REMOVED

License #: 011377 Licensee Name: BENJAMIN BELOT
Firm: 003843 Firm Name: LEADER ELECTRIC CO., INC
Firm Phone: 212-665-0606  Firm Address: 857 SOUTHERN BLVD BRONX NY 10459 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $700.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JEFFREY KAYE
Owner Business Name: STONE STREET PROPERTIES
Authorized Representative:  JEFFREY KAYE
Relationship To Owner:   MANAGEMENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400 AMPS
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  21  20 APT 1 PLP
B. Over #2 to 1/0  1  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  2  TO SW, TO METERBANK
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS  BSMT               
Buildings Total                 
Total Units : 5 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 21 #4-Wire 0 #10-Wire 0
Existing Meters 21 + New Meters 21 - Removed Meters 21 = Total Meters 21

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 07/01/2014 Notice: C - CALL TO OFFICE 12/15/2017
Power Issued: 07/01/2014 Response:  

Follow-Up:
Contractor's Comments:  INSTALLING NEW SERVICE AND METERING. NEW PLP. TIE INTO EXISTING FEEDERS. FEEDERS AND OTHER WORK DONE BY OTHERS.

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M355595
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/17/2015 03/20/2015 EID Z (0) (0) Y
INSPECTION COMMENTS: NONE
 
(2) 04/06/2015 04/09/2015 DNM N (30) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 09/28/2015 10/07/2015 NRS A G (60) (9) Y
INSPECTION COMMENTS: ENDLINE BOX TEMP ED - UP(WAITING FOR CON ED. APT RISERS EXTENDED
 
(4) 08/11/2016 08/12/2016 PHG N (15) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR SAID HE DID NOT REQUEST AN APT AT LOCATION NO SHOW
 
(5) 12/14/2017 12/15/2017 BMP J X (10) (0) Y
INSPECTION COMMENTS: JOB IN PROGRESS.

OBJECTION FOR APPLICATION #: M355595
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: NO INTER SYSTEM GR.BAR.. 250.94
OPEN 09/28/2015 09/28/2015
 
002 (280) MAIN BONDING JUMPER IS DEFECTIVE
BSMNT: NOT AS PER 250.66
OPEN 09/28/2015 09/28/2015
 
003 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BSMNT: COLLECTOR BAR250.66
OPEN 09/28/2015 09/28/2015
 
004 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
BSMNT: E.G.C.BETWEEN METER B.TERM.BOX & 60A PLP DISC NOT AS PER250.66
OPEN 09/28/2015 09/28/2015
 
005 (999) OTHER
BSMNT: OPENINGS NOT FIRE PROOFED.. 300.21
OPEN 09/28/2015 09/28/2015
 
006 (999) OTHER
BSMNT: GEC CONDUIT NOT CONTINUOUS.. 250.66(E)
OPEN 09/28/2015 09/28/2015
 
007 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
BSMNT: 5" X 5" OLD FUSE BOS WITH DOOR BELL IN HALLWAY
OPEN 09/28/2015 09/28/2015
 
008 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
BSMNT: 8" X 8" NEW SPLICE BOXES(3)IN HALLWAY.. 250.8
OPEN 09/28/2015 09/28/2015
 
009 (999) OTHER
BASE: G.E.C.CONDUIT NOT CONTINUOUS.. 250.24(A)(4)
OPEN 09/28/2015 09/28/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.