Electrical Application Details for App #: Z145686
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 143 WEST 104 STREET MANHATTAN BIN: 1076625     Block: 1859   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 150 W 105 ST Census Tract:   189 Health Area:  3210
CELLAR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10025 Community Board:   107
Special Place Name:   PS 145
DOB Cross Street(s):   COLUMBUS AVENUE,    AMSTERDAM AVENUE
Status:   C - JOB IS SIGNED OFF 12/09/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/15/2014 2:28 PM
Application Entered:   08/15/2014 Job Start Date:   08/15/2014
Last Change:   12/09/2019 Job End Date:   12/31/2015
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     11/12/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011058 Licensee Name: NAUM VAYNERMAN
Firm: 002408 Firm Name: FALCON ELEC'L CONTR'G COR
Firm Phone: 718-840-2800  Firm Address: 159 20TH STREET SUITE 4A BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $289.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: NYC SCA
Owner Business Name: SCHOOL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  4#3/0
D. Over 250 MCM  1  4#500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  200
D. 3 Phase Over 225 AMPS  1  400
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL          25             
Buildings Total       25                
Total Units : 28 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/01/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: Z145686
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/13/2019 05/13/2019 VTC V (65) (9)
INSPECTION COMMENTS: FAIL
 
(2) 11/01/2019 11/01/2019 GYM V R (55) (1)
INSPECTION COMMENTS: NEW PERMIT REQUIRED NEW BOILERS & NEW MOTORS.
 
(3) 11/12/2019 11/12/2019 GYM C R (55) (0)
INSPECTION COMMENTS: SEE APP # M0026007

OBJECTION FOR APPLICATION #: Z145686
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(BASEMENT) NEUTRAL BONDED AT BOTH DISCONNECTS IN ELECTRIC ROOM
RSLV 05/13/2019 05/13/2019 11/01/2019
 
002 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(BASEMENT) PROPER DIRECTORY NOT PROVIDED
RSLV 05/13/2019 05/13/2019 11/01/2019
 
003 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(BASEMENT) EMT SUPPORT NEEDED IN PUMP ROOM
RSLV 05/13/2019 05/13/2019 11/01/2019
 
004 (999) OTHER
(BASEMENT) FIRESTOP NOT PROVIDED FOR PENETRATIONS 300.21
RSLV 05/13/2019 05/13/2019 11/01/2019
 
005 (999) OTHER
(BASEMENT) DURABLE LABELS NOT PROVIDED FOR EQUIPMENT 110.22
RSLV 05/13/2019 05/13/2019 11/01/2019
 
006 (999) OTHER
(BASEMENT) PANEL PLANKS NEEDED 408.7
RSLV 05/13/2019 05/13/2019 11/01/2019
 
007 (999) OTHER
(BASEMENT) GREENFIELD NOT PROPERLY SUPPORTED IN BOILER ROOM
RSLV 05/13/2019 05/13/2019 11/01/2019
 
008 (999) OTHER
(BASEMENT) ARC FLASH LABELS NOT PROVIDED FOR EQUIPMENT 110.16
RSLV 05/13/2019 05/13/2019 11/01/2019
 
009 (999) OTHER
(BASEMENT) KO SEALS NEEDED IN PANEI 110.12
RSLV 05/13/2019 05/13/2019 11/01/2019
 
010 (999) OTHER
(CELLAR) PAA REQUIRED OBSERVED 2 NEW BOILERS, MOTORS.
RSLV 11/01/2019 11/01/2019 11/12/2019