Electrical Application Details for App #: M395280
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 218 EAST 6 STREET MANHATTAN BIN: 1006615     Block: 461   Lot: 17
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 218 E 6TH ST Census Tract:   38 Health Area:  6500
4 Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10003 Community Board:   103
Special Place Name:   JABOBSON RESIDENCE
DOB Cross Street(s):   TARAS SHEVCHENKO PLACE,    2 AVENUE
Status:   C - JOB IS SIGNED OFF 09/25/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/27/2017 1:29 PM
Application Entered:   04/27/2017 Job Start Date:   04/27/2017
Last Change:   09/25/2017 Job End Date:   05/10/2017
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     09/25/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012374 Licensee Name: SHEFKI ARIFI
Firm: 002528 Firm Name: KLEAR ELECTRICAL CORP.
Firm Phone: 718-361-5366  Firm Address: 31-00 47TH AVENUE LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $76.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PETER JAKOBSON
Owner Business Name: 218 E 6 TH ST ASSOCIATES
Authorized Representative:  MIKE KURTISH
Relationship To Owner:   CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004  13  17               
Buildings Total 17                  
Total Units : 35 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/28/2017 Notice: 1 - FIRST NOTICE 07/12/2017
Power Issued: 04/28/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M395280
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/20/2017 06/20/2017 BMP J (15) (0) Y
INSPECTION COMMENTS: JOB IN PROGRESS.
 
(2) 07/12/2017 07/12/2017 CBK V (45) (7)
INSPECTION COMMENTS: FAIL
 
(3) 08/08/2017 08/08/2017 TOR N (15) (0) Y
INSPECTION COMMENTS: NO ACCESS TO APT CONTRACTOR PRESENT
 
(4) 09/25/2017 09/25/2017 BMP C R (35) (0)
INSPECTION COMMENTS: CERTIFIED.

OBJECTION FOR APPLICATION #: M395280
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(FLOOR: 004) MCS GROUND WIRES TERMINATED ON NEUTRAL BAR.
RSLV 07/12/2017 07/12/2017 09/25/2017
 
002 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(FLOOR: 004) MC CABLE NOT TERMINATED, IN DISHWASHER.
RSLV 07/12/2017 07/12/2017 09/25/2017
 
003 (282) MINIMUM NUMBER OF SMALL APPLIANCE CIRCUITS
(FLOOR: 004) ONE COUNTER TOP CIRCUIT PROVIDED.
RSLV 07/12/2017 07/12/2017 09/25/2017
 
004 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(FLOOR: 004) OPEN KOS IN PANEL.
RSLV 07/12/2017 07/12/2017 09/25/2017
 
005 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 004) PANEL DIRECTORY NOT PROPERLY DONE.
RSLV 07/12/2017 07/12/2017 09/25/2017
 
006 (999) OTHER
(FLOOR: 004)RECEPTACLE BOX SET BACK IN COMBUSTIBLE MATERIAL FOR MICROWAVE.314.20
RSLV 07/12/2017 07/12/2017 09/25/2017
 
007 (999) OTHER
(BASEMENT) MC GROUND WIRE NOT TERMINATED. 250.118.
RSLV 07/12/2017 07/12/2017 09/25/2017