BIS Menu  |  Property Profile  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M349686
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 43 1 AVENUE MANHATTAN BIN: 1006132     Block: 444   Lot: 34
   
Application Completed and Certified

Filed: 45 1 AV Census Tract:   36.02 Health Area:  6500
1ST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10003 Community Board:   103
DOB Cross Street(s):   EAST 2 STREET,    EAST 3 STREET
Status:   C - JOB IS SIGNED OFF 09/27/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/26/2014 9:54 PM
Application Entered:   01/26/2014 Job Start Date:   01/27/2014
Last Change:   09/27/2014 Job End Date:   04/27/2014
Appointment Status:   
Last Inspection By:   ELLIS DAVID       On     09/22/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011616 Licensee Name: CESAR TIPIAN
Firm: 004145 Firm Name: C.T.C. ELEC'L CONTRS INC
Firm Phone: 347-810-9954  Firm Address: 435 AUSTIN PLACE, SUITE D BRONX NY 10455 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $51.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RETAIL STORE
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JORGE ARIAS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    18  10    18             
Buildings Total 18  10    18                
Total Units : 54 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 08/06/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  PARTIAL WIRING

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M349686
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/01/2014 08/06/2014 PHG V (30) (6) Y
INSPECTION COMMENTS: LICENSE SENT GC VISUAL. INSPECTION ONLY FULL NEEDED
 
(2) 09/22/2014 09/26/2014 EID C R (25) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M349686
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
45-1 LIGHT FIXTURE IN FRONT NOT GROUND 250.112
RSLV 08/01/2014 08/01/2014 09/22/2014
 
002 (999) OTHER
45-1 NO GFCI BY OUTDOOR CONDENSER 210.62
RSLV 08/01/2014 08/01/2014 09/22/2014
 
003 ( 19) DEFECTIVE WIRING IS IN USE
BASEMENT RECEPTICLE FEED WITH FLEX CORD
RSLV 08/01/2014 08/01/2014 09/22/2014
 
004 ( 29) OUTLET BOXES ARE NOT COVERED
BASEMENT RECEPTICLE NOT COVERED. 314.25
RSLV 08/01/2014 08/01/2014 09/22/2014
 
005 (999) OTHER
OUTDOOR NO DISCONNECT FOR A/C 430.22
RSLV 08/01/2014 08/01/2014 09/22/2014
 
006 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
BASEMENT NO DIRECTORY FOR PANEL 408.4
RSLV 08/01/2014 08/01/2014 09/22/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.