Electrical Application Details for App #: M396540
NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
Premises: 212 BROADWAY MANHATTAN BIN: 1001245     Block: 89   Lot: 12
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 222 BROADWAY Census Tract:   15.01 Health Area:  7700
GROUND FL & 2FL Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10038 Community Board:   101
Special Place Name:   PRET-A-MANGER
DOB Cross Street(s):   FULTON STREET,    ANN STREET
Status:   C - JOB IS SIGNED OFF 09/26/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/24/2017 3:28 PM
Application Entered:   05/24/2017 Job Start Date:   05/24/2017
Last Change:   09/26/2017 Job End Date:   09/01/2017
Appointment Status:   
Last Inspection By:   VINCENT CASTALDO       On     09/26/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011332 Licensee Name: SPIRO SINANIS
Firm: 003482 Firm Name: METROPOLIS ELECTRIC CORP
Firm Phone: 718-205-7605  Firm Address: 110 WEST 40 STREET SUITE 600 NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $423.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: LL HOLDING COMPANY, LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  600A 3PH
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  3  1-3#500MCM & 2-4#350MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002                      225 
Buildings Total                        225 
Total Units : 225 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/21/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REUSED EXISTING 400AS TO SERVE TRANSFORMER. POWER MAKE-READY TO GROUND FLOOR RETAIL STORE JB.

 
Inspection Details
 

*NO PRE-BIS PLACE OF ASSEMBLY CERTIFICATES FOUND
INSPECTION FOR APPLICATION #: M396540
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/20/2017 07/21/2017 STP V (65) (1)
INSPECTION COMMENTS: FAIL. ALL FEEDERS NEED TO BE FILED FOR. DID NOT CONFIRM LOAD SIDE WIRES TERMINATING POINT OFF 600 AMP SWITCH.
 
(2) 09/26/2017 09/26/2017 VTC C R (50) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M396540
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 002) SBJ NOT CONNECTED TO ENCLOSURE 250.30
RSLV 07/20/2017 07/20/2017 09/26/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.