BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Property Permits  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B307698
NO PREVIOUSLY ISSUED PERMITS FOUND FOR THIS PROPERTY
Premises: 4819 4 AVENUE BROOKLYN BIN: 3012572     Block: 774   Lot: 2
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 4819 4 AV Census Tract:   78 Health Area:  6500
BASEMENT,1A,2A,3A,4A Admin Area:   B - BROOKLYN Inspection Area:   J
BROOKLYN, NY 11220 Community Board:   307
DOB Cross Street(s):    48 STREET,    49 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/12/2008 3:01 PM
Application Entered:   08/12/2008 Job Start Date:   08/13/2008
Last Change:   08/22/2025 Job End Date:   08/11/2009
Appointment Status:   
Last Inspection By:   ROBINSON HEATH       On     07/13/2015      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  D - DON'T ISSUE POWER AUTH
Objection Disposition:  

License #: 011729 Licensee Name: WILFRED JEFFREY
Firm: 003318 Firm Name: J.K.ELECTRICAL CONTRACTOR
Firm Phone: 718-369-0539  Firm Address: 247 PROSPECT AVENUE BROOKLYN NY 11225 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $208.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JACK GUELA
Owner Business Name: 4 SUNSET PARK HOLDING
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  5  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  4  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total   72  32  32                
Total Units : 144 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 4 #4-Wire 0 #10-Wire 0
Existing Meters 12 + New Meters 4 - Removed Meters 0 = Total Meters 16

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 08/12/2008 Notice: 1 - FIRST NOTICE 07/23/2015
Power Issued: 08/12/2008 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

*NO PREVIOUSLY ISSUED PERMITS FOUND FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: B307698
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/13/2015 07/23/2015 HRB V D (135) (4) Y
INSPECTION COMMENTS: NEED ACCESS TO ALL APTS

OBJECTION FOR APPLICATION #: B307698
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 42) BUSHINGS ARE MISSING OR LOOSE
BASEMENT-EQUIMENT AND PANELS IN APT
OPEN 07/13/2015 07/13/2015
 
002 (999) OTHER
BASEMENT-NEUTRAL BONDED AFTER MAIN SWITCH(IN METER PANS)(250.92A)
OPEN 07/13/2015 07/13/2015
 
003 (999) OTHER
APT.1-PANEL INSTALLED IN CLOTHES CLOSET
OPEN 07/13/2015 07/13/2015
 
004 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
APT. 3-DEFECTIVE AFCI
OPEN 07/13/2015 07/13/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Property Permits  |  Back