| NYC Department of Buildings | ||
| Overview for Complaint #:1643293 = RESOLVED | ||
| Complaint at: 20 EAST 46 STREET | BIN: 1035395 | Borough: MANHATTAN | ZIP: 10017 | |||
| Re: NO APP ON FILE FOR 1- 30AMP DISCONNECT AND 1 STROBE PANEL,#10 AWG WIRE TAPPED FROM SUBPANEL AND DOUBLE LUGGED IN 200 AMP PANEL | ||||||
| Category Code: | 59 ELECTRICAL WIRING - DEFECTIVE/EXPOSED, IN PROGRESS | |
| Special District: | MID - MIDTOWN | |
| Assigned To: | ELECTRICAL DIVISION | Priority: B |
| Received: | 07/17/2023 | Block: 1281 | Lot: 59 | Community Board: 105 | ||
| Owner: | 18-20/22 EAST 46TH | |||||
| Last Inspection: | 07/19/2023 - - BY BADGE # 1244 |
| Disposition: | 07/20/2023 - A8 - ECB VIOLATION SERVED |
| ECB Violation #: | 39090600Z 39090601K |
| Comments: | "PLEASE NOTE" AT THE TIME OF MY INSPECTION ON THE 3TH FLOOR OFFICE SPACE. I OBSERVED 30 AMP SERVICE DISCONNECT FOR A FIRE ALARM SYSTEM.(2) THE SERVICE ENTRANCE FOR THAT SYSTEM ON THE LINE SIDE OF THE BUILDINGS SERVICE SWITCHES AS PER ARTICLE 760 IN THE NEC. APPLICATION # M00873394, M00051115. DOESN'T COVERED THE ABOVE INFRACTIONS. |
| Complaint Disposition History |
| # | Disposition | Disposition | Inspection | Date | |
| Date | Code | By | |||