BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M386343
NO MARQUEE RECORDS FOUND FOR THIS PROPERTY
Premises: 15 EAST 12 STREET MANHATTAN BIN: 1076982     Block: 570   Lot: 38
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 15 E12 ST Census Tract:   61 Health Area:  5700
GND FL Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    UNIVERSITY PLACE
Status:   C - JOB IS SIGNED OFF 06/19/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/12/2016 10:28 AM
Application Entered:   09/12/2016 Job Start Date:   09/14/2016
Last Change:   06/19/2017 Job End Date:   11/25/2016
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     06/05/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009165 Licensee Name: CARMINE J CAMENZULI
Firm: 003589 Firm Name: JLC ELEC'L CONTR'G INC
Firm Phone: 718-932-2499  Firm Address: 14-45 BROADWAY LONG ISLAND CITY NY 11106 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $107.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RUPILA SETHI
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  NEW PANEL
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND  GND  30  35                 
ROF                     
Buildings Total 30  35                  
Total Units : 80 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/08/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO MARQUEE RECORDS FOUND FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M386343
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/27/2017 02/27/2017 TOR J (40) (0) Y
INSPECTION COMMENTS: CONTRACTOR NOT FAMILIAR WITH A JOB NEED UPDATE APP .( MISSING INFORMATION)
 
(2) 03/28/2017 03/30/2017 JUU V (55) (9)
INSPECTION COMMENTS: FULL RE-INSPECTION NEEDED , NEED LOAD CALCULATIONS / RISER FOR RESTAURANT SEE OBJECTIONS
 
(3) 05/08/2017 05/08/2017 GYM V Y (75) (3)
INSPECTION COMMENTS: ADD PANEL, HVAC UNIT.
 
(4) 06/05/2017 06/06/2017 EDB C R (50) (0)
INSPECTION COMMENTS: INSPECT OBJECTION ONLY.

OBJECTION FOR APPLICATION #: M386343
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (136) GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS
(CELLAR) INSTALL GROUND AT SERVICE
RSLV 03/28/2017 03/28/2017 05/08/2017
 
002 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
(CELLAR) DE-RATE BUNDLE OF BX CABLES IN SERVICE ROOM
RSLV 03/28/2017 03/28/2017 05/08/2017
 
003 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(CELLAR) SUPPORT CONDUITS IN BETWEEN PANELS
RSLV 03/28/2017 03/28/2017 05/08/2017
 
004 (999) OTHER
(CELLAR)PROVIDE RISER DRAWING / LOAD LETTER WITH ALL LOADS FOR RESTAURANT
RSLV 03/28/2017 03/28/2017 06/05/2017
 
005 (999) OTHER
(CELLAR) KNOCKOUTS OPEN THROUGHOUT
RSLV 03/28/2017 03/28/2017 05/08/2017
 
006 (999) OTHER
(CELLAR) SUPPORT LIGHTING IN KITCHEN , IN CORRECT CLIPS IN USE
RSLV 03/28/2017 03/28/2017 06/05/2017
 
007 (999) OTHER
(CELLAR) PROVIDE NETURAL BOND AT 200A SERVICE SWITCH
RSLV 03/28/2017 03/28/2017 05/08/2017
 
008 (999) OTHER
(CELLAR) PROVIDE BOX EXTENDERS AT COMBUSTIBLE WALLS
RSLV 03/28/2017 03/28/2017 05/08/2017
 
009 (999) OTHER
(CELLAR) PROVIDE TYPEWRITTEN DIRECTORYS
RSLV 03/28/2017 03/28/2017 06/05/2017
 
010 (999) OTHER
(BASEMENT)WIRING METHODS SHALL NOT BE EXPOSED WITHIN THE COOKING HOOD 410.10
RSLV 05/08/2017 05/08/2017 06/05/2017
 
011 (999) OTHER
(BASEMENT) COMMERCIAL KITCHEN GFCI REQUIRED ALL RECEPTACLES 210.8
RSLV 05/08/2017 05/08/2017 06/05/2017
 
012 (999) OTHER
(ROOF) LFMC OVER 6FL 350.12
RSLV 05/08/2017 05/08/2017 06/05/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back