BIS Menu  |  Marquee Query  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A034262
NO MARQUEE RECORDS FOUND FOR THIS PROPERTY
Premises: 35-25 29 STREET QUEENS BIN: 4004108     Block: 341   Lot: 13
   
Application Completed and Certified

Filed: 35-25 29 ST Census Tract:   53 Health Area:  0710
4TH FLOOR Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11106 Community Board:   401
DOB Cross Street(s):    35 AVENUE,    36 AVENUE
Status:   C - JOB IS SIGNED OFF 03/24/1989
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   10/25/1988 Job Start Date:   10/19/1988
Last Change:   03/20/1989 Job End Date:   11/19/1988
Appointment Status:   
Last Inspection By:   GALIZIA, J.       On     03/09/1989      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009931 Licensee Name: A SQUILLANTE
Firm: 000043 Firm Name: A.T.S. ELEC'L SVC. INC.
Firm Phone: 718-325-5554  Firm Address: 4365 WEBSTER AVENUE BRONX NY 10470 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $651.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: GEARY & ANGEL ROASSOS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  4  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  30  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total   60                      
Total Units : 60 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

Access:   8AM TO 4PM Contact Phone:   325-5554

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 32 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: R - OBJECTION(S) RESOL
Power Requested: 10/25/1988 Notice:  12/27/1988
Power Issued: 10/25/1988 Response: R - REINSPECTION 01/18/1989

Follow-Up: K - (CLOSED)
Wires Comments: ONE 400A MAIN 4 WIRE 30-115/208 3 WIRE METER ONE 4 WIRE METER
Contractor's Comments:  NONE

 
Inspection Details
 

*NO MARQUEE RECORDS FOUND FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: A034262
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/12/1988 12/27/1988 JG1 A G (60) (4)
INSPECTION COMMENTS: *1 NEUTRAL BAS IS NOT BONDED TO THE ENCL/*2 BOND.JUMPPER IS UNDER SZ FROM SER ENT BUSH.TO ENCL/*3NEUT BAR IS BOND AFTER THE SERSW
 
(2) 03/09/1989 03/20/1989 JG1 C R E (50) (0)
INSPECTION COMMENTS: N/C




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Marquee Query  |  Electrical Inspection Work Order  |  Back