| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
2 |
3/0 |
| D. 3 Phase Over 225 AMPS |
1 |
600MCM |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED BASEMENT NO SQUARE OF GROUND FOR ISOLATED GROUND BAR IN PANEL(250.112) |
RSLV |
09/12/2014 |
09/12/2014 |
10/22/2014 |
| |
| 002 |
(999) |
OTHER BASEMENT EGC COND. DOUBLED UP IN BASEMENT A/C DISC (110.14 (A) |
RSLV |
09/12/2014 |
09/12/2014 |
10/22/2014 |
| |
| 003 |
(307) |
NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT BASEMENT SERVICE RECEP NOT PROVIDED FOR A/C EQUIP (210.63) |
RSLV |
09/12/2014 |
09/12/2014 |
10/22/2014 |
| |
| 004 |
(999) |
OTHER BASEMENT OVER 31 CURRENT CARRYING COND IN TROUGH (310.15B(2A) |
RSLV |
09/12/2014 |
10/22/2014 |
12/01/2014 |
| |
| 005 |
(307) |
NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT 1ST FL NO SERVICE RECEP PROVIDE AT A/C UNITS 210.63 |
RSLV |
10/22/2014 |
12/01/2014 |
01/20/2015 |
| |
| 006 |
(999) |
OTHER 1ST FL A/C UNITS NOT SPEC. AS PER MAN SPEC. 110.3 |
RSLV |
10/22/2014 |
12/01/2014 |
01/20/2015 |
| |
| 007 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) BSMT: EMT NOT PROPERLY SECURED (EL RM). 358.30 |
RSLV |
12/01/2014 |
12/01/2014 |
01/20/2015 |
| |
| 008 |
(999) |
OTHER BSMT: PANELS MULTIWIRE CKT NO GROUPED,NO SIMULT TRIP. 210.4 |
RSLV |
12/01/2014 |
01/20/2015 |
02/04/2015 |
| |
| 009 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED BSMT: EL.RM. FMC NO EQUIPMENT GND. 250.118,112 |
RSLV |
12/01/2014 |
12/01/2014 |
01/20/2015 |
| |
| 010 |
(999) |
OTHER BSMT: EL.RM/METER RM PULL BOX TOO SMALL. 314.28 |
RSLV |
12/01/2014 |
12/01/2014 |
01/20/2015 |