BIS Menu  |  Elev. Device Details  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M351071
NO MARQUEE RECORDS FOUND FOR THIS PROPERTY
Premises: 10 EAST 52 STREET MANHATTAN BIN: 1035478     Block: 1287   Lot: 63
   
Application Completed and Certified

Filed: 10 E 52 ST Census Tract:   102 Health Area:  4800
4TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
Special Place Name:   CARTIER-RICHEMONT
DOB Cross Street(s):    5 AVENUE,    MADISON AVENUE
Status:   C - JOB IS SIGNED OFF 11/06/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/05/2014 3:51 PM
Application Entered:   03/05/2014 Job Start Date:   03/05/2014
Last Change:   11/06/2014 Job End Date:   04/18/2014
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     09/18/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011229 Licensee Name: RICHARD SOBEL
Firm: 002851 Firm Name: QUANTUM ELECTRIC CORP.
Firm Phone: 718-784-9010  Firm Address: 41-11 28TH STREET LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
L - LIGHTING WORK
Total Fee:  $130.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  121927585
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: TISHMAN SPEYER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  4#4
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  (1) 100A
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004    16  33    56             
Buildings Total 16  33    56                
Total Units : 112 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/29/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  RICHEMONT 4TH FLOOR QEC #9107

 
Inspection Details
 

*NO MARQUEE RECORDS FOUND FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M351071
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/23/2014 07/29/2014 PHG A (50) (7) Y
INSPECTION COMMENTS: NONE
 
(2) 09/18/2014 09/24/2014 DNM C R (20) (0) Y
INSPECTION COMMENTS: ALL VIOLATIONS REMOVED

OBJECTION FOR APPLICATION #: M351071
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
4FL: NO G.F.C.I.PROVIDED IN PANTRY. 210.8
RSLV 07/23/2014 07/23/2014 09/18/2014
 
002 ( 29) OUTLET BOXES ARE NOT COVERED
4FL: MICROWAVE RECEPTACLE LEFT OPEN. 314.25
RSLV 07/23/2014 07/23/2014 09/18/2014
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
4FL: 1" PIPE NOT PROPERLY CONNECTED IN PANEL. 250.122
RSLV 07/23/2014 07/23/2014 09/18/2014
 
004 (999) OTHER
4FL: LINE AND LOW VOLT IN SAME BOX FOR ALL LED LIGHTS. ART.725
RSLV 07/23/2014 07/23/2014 09/18/2014
 
005 (999) OTHER
4FL: RECEPTACLES IN VYNL SET BACK TOO FAR. 314.20
RSLV 07/23/2014 07/23/2014 09/18/2014
 
006 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
4FL: UNTERMINATED CABLES IN CEILING. 320.40
RSLV 07/23/2014 07/23/2014 09/18/2014
 
007 ( 29) OUTLET BOXES ARE NOT COVERED
4FL: OPEN BOXES IN ALL CEILING. 314.25
RSLV 07/23/2014 07/23/2014 09/18/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Elev. Device Details  |  Electrical Inspection Work Order  |  Back