NYC Department of Buildings
Electrical Application Details for App #: B322871
NO MARQUEE RECORDS FOUND FOR THIS PROPERTY
Premises: 626 EAST 16 STREET BROOKLYN BIN: 3121187     Block: 5236   Lot: 23
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 15 NEWKIRK PLAZA Census Tract:   520 Health Area:  7210
1ST FLOOR Admin Area:   B - BROOKLYN Inspection Area:   K
BROOKLYN, NY 11226 Community Board:   314
DOB Cross Street(s):   NEWKIRK AVENUE,    FOSTER AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/10/2009 11:32 AM
Application Entered:   12/10/2009 Job Start Date:   12/11/2009
Last Change:   08/22/2025 Job End Date:   02/28/2010
Appointment Status:   
Last Inspection By:   DOYLEY, DEXTER       On     08/02/2010      
Field Disp:   N - NO ACCESS
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 010069 Licensee Name: PETER AMABILE
Firm: 003346 Firm Name: FLEMINGTON ELEC'L MAINT I
Firm Phone: 646-230-9903  Firm Address: 225 31 STREET BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $103.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   BANK
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BARBARA GIORDANO
Owner Business Name: BOA / BNF CONTRACTORS
Authorized Representative:  BARBARA GIORDANO
Relationship To Owner:   CONSTRUCTION MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  SET OF # 2'S
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  40 CIRCUIT PANEL
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    19    19     
Buildings Total 19    19            
Total Units : 53 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 1 + New Meters 0 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 12/10/2009 Notice: 1 - FIRST NOTICE 04/02/2010
Power Issued: 12/10/2009 Response:  

Follow-Up:
Contractor's Comments:  BANK OF AMERICA ATM CROSS STREET E16TH ST

 
Inspection Details
 

*NO MARQUEE RECORDS FOUND FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: B322871
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/31/2010 04/02/2010 MC2 V E (45) (9) Y
INSPECTION COMMENTS: NOT A FINAL
 
(2) 08/02/2010 08/09/2010 DEX N (60) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B322871
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
A/C COMPRESSOR DIS SWITCH MIN 3FT SPACE NOT PROVIDED 110.26
OPEN 03/31/2010 03/31/2010
 
002 (999) OTHER
A/C DIS SW GROUNDING CONDUCTORS STRANDED NOT TERMINATED IN LUG
OPEN 03/31/2010 03/31/2010
 
003 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
A/C BLOWER FLEXIBLE AS PERMANENT WIRING METHOD 408.8
OPEN 03/31/2010 03/31/2010
 
004 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
WIRES RUN IN EMT TO 42 CKT PANEL BLUE CONDUCTOR REIDENTIFIED WITHTYPE NOT #4 LARGER NOT PROVIDED 210.43 210.J
OPEN 03/31/2010 03/31/2010
 
005 ( 19) DEFECTIVE WIRING IS IN USE
F.A GND DOUBLE LUGED AT WATER MAIN 110.14A
OPEN 03/31/2010 03/31/2010
 
006 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
GND CONDUCTORS NOT PROPERLY TERMINATED 250.24
OPEN 03/31/2010 03/31/2010
 
007 (999) OTHER
F.A CUT OUT WIRES TERMINATION USE DOUBLE LUGED 110.14PANEL RISERS IN BSMT ARMORED CABLES NOT SUPPORTED 320.3A
OPEN 03/31/2010 03/31/2010
 
008 (999) OTHER
RISE DIS PANEL F.A TAPS DOUBLE LUGGED 110.14A
OPEN 03/31/2010 03/31/2010
 
009 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
RISE DIS PANEL KO SEALS NOT PROVIDED 110.12A
OPEN 03/31/2010 03/31/2010