Electrical Application Details for App #: A367652
NO MARQUEE RECORDS FOUND FOR THIS PROPERTY
Premises: 35-08 28 STREET QUEENS BIN: 4004024     Block: 339   Lot: 49
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 3508 28 ST Census Tract:   47 Health Area:  0710
BASEMENT Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11106 Community Board:   401
DOB Cross Street(s):    35 AVENUE,    36 AVENUE
Status:   C - JOB IS SIGNED OFF 05/11/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/01/2017 11:38 AM
Application Entered:   10/01/2017 Job Start Date:   10/01/2017
Last Change:   05/11/2018 Job End Date:   03/12/2018
Appointment Status:   
Last Inspection By:   SCHUSZTER, NORBET       On     05/07/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012564 Licensee Name: VALMA D BOYCE
Firm: 004390 Firm Name: V&B ELECTRICAL CONTNG INC
Firm Phone: 917-821-9664  Firm Address: 220-31 JAMAICA AVENUE QUEENS NY 11428 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $79.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SUSANE MOKLEL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  3  100 AMP
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  100 AMP
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 3 #4-Wire 0 #10-Wire 0
Existing Meters 2 + New Meters 1 - Removed Meters 0 = Total Meters 3

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/01/2017 Notice: 1 - FIRST NOTICE 04/10/2018
Power Issued: 10/01/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  METER WORK.

 
Inspection Details
 

*NO MARQUEE RECORDS FOUND FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: A367652
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/18/2018 01/18/2018 ECH N (42) (0) Y
INSPECTION COMMENTS: TENANT WAS HOME BUT CONTRACTOR NO SHOW
 
(2) 03/16/2018 03/16/2018 ECH N (46) (0) Y
INSPECTION COMMENTS: CONTRACTOR WAS PRESENT BUT NO ACCESS TO HOUSE
 
(3) 04/10/2018 04/10/2018 ECH V (35) (4)
INSPECTION COMMENTS: SEE OBJECTIONS
 
(4) 05/07/2018 05/07/2018 NRS C R (31) (0)
INSPECTION COMMENTS: SERVICE WORK ONLY. OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: A367652
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
(BASEMENT) INSTALLED ATTACHED TO BROKEN KO
RSLV 04/10/2018 04/10/2018 05/07/2018
 
002 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(BASEMENT) OPEN KO'S IN PANEL
RSLV 04/10/2018 04/10/2018 05/07/2018
 
003 ( 53) GFCI HAS NOT BEEN PROVIDED
(BASEMENT)UNINHABITABLE BASEMENT ALL RECEPTACLES TO BE GFCI PROTECTED 210.8
RSLV 04/10/2018 04/10/2018 05/07/2018
 
004 (999) OTHER
(BASEMENT)ALL BASEMENT CIRCUITS HAVE BEEN MOVED TO PLP PANEL. NYC 27-301(3)(I)
RSLV 04/10/2018 04/10/2018 05/07/2018