BIS Menu  |  Electrical Inspection Work Order  |  Applications  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M286544
NO MARQUEE RECORDS FOUND FOR THIS PROPERTY
Premises: 159 ESSEX STREET MANHATTAN BIN: 1083470     Block: 412   Lot: 73
   
Application Completed and Certified

Filed: 159 ESSEX ST Census Tract:   30.01 Health Area:  6600
1,2,3,4 Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10002 Community Board:   103
DOB Cross Street(s):   STANTON STREET,    AVENUE A
Status:   C - JOB IS SIGNED OFF 05/15/2009
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/03/2008 3:33 PM
Application Entered:   11/03/2008 Job Start Date:   11/03/2008
Last Change:   05/15/2009 Job End Date:   01/03/2009
Appointment Status:   
Last Inspection By:   BEST, J       On     04/09/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011252 Licensee Name: ALBERT V DATTOLO
Firm: 001211 Firm Name: RAINBOW ELECTRIC CO., INC
Firm Phone: 718-521-0926  Firm Address: 76-18 ROCKAWAY BLVD WOODHAVEN NY 11421 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $513.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: KATHY CHEUNG
Owner Business Name: YIN FA REALTY CORP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  COMBO PANELS
B. 101 Up to 200 AMPS  3  COMBO PANEL
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  4  1 SET #3/0 WIRE
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 12 #4-Wire 1 #10-Wire 0
Existing Meters 13 + New Meters 13 - Removed Meters 13 = Total Meters 13

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/03/2008 Notice: 1 - FIRST NOTICE 01/30/2009
Power Issued: 11/03/2008 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  FILING FOR METER UPGRADE ONLY

 
Inspection Details
 

*NO MARQUEE RECORDS FOUND FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M286544
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/27/2009 01/30/2009 JSB A E (60) (4) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 04/09/2009 04/16/2009 JSB C R E (45) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M286544
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: 100 AMP DISC SW FOR SALON COND OVER FUSED310.16
RSLV 01/27/2009 01/27/2009 04/09/2009
 
002 (999) OTHER
A) BSMT: CKT BKR PANEL FOR DELI DOUBLE F TAPS ON LUGS110.14(A)
RSLV 01/27/2009 01/27/2009 04/09/2009
 
003 (999) OTHER
B) BSMT: TROUGH SPLICES TOO MANY WIRES ON SPLIT BOLT CONN110.14(A)
RSLV 01/27/2009 01/27/2009 04/09/2009
 
004 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
BSMT: APARTMENT DISC PANEL
RSLV 01/27/2009 01/27/2009 04/09/2009



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order  |  Applications  |  Back