BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M375690
NO MARQUEE RECORDS FOUND FOR THIS PROPERTY
Premises: 55 EAST 52 STREET MANHATTAN BIN: 1083869     Block: 1288   Lot: 27
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 55 E 52ND ST Census Tract:   102 Health Area:  4800
23RD FLOOR Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
Special Place Name:   EVERCORE
DOB Cross Street(s):   MADISON AVENUE,    PARK AVENUE
Status:   C - JOB IS SIGNED OFF 10/29/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/08/2015 3:13 PM
Application Entered:   12/08/2015 Job Start Date:   12/09/2015
Last Change:   10/29/2016 Job End Date:   02/15/2016
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     10/24/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011456 Licensee Name: RALPH OCCHIPINTI
Firm: 000064 Firm Name: ADCO ELEC'L CORP
Firm Phone: 718-494-4400  Firm Address: 201 EDWARD CURRY AVENUE STATEN ISLAND NY 10314 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
Total Fee:  $138.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  122458740
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: KEVIN T LILLIS
Owner Business Name: FISHER BROTHERS MGMT CO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2   4#4
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  1-60A MCB
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
023    33    25      15 
Buildings Total 33    25             15 
Total Units : 85 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/20/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  JM JOB #150272 - FURNISH AND INSTALL LIGHTING AND POWER FORPARTIAL FITOUT. NO CHANGE TO EXISTING SERVICE.

 
Inspection Details
 

*NO MARQUEE RECORDS FOUND FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M375690
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/19/2016 10/20/2016 BUR V (60) (1)
INSPECTION COMMENTS: PARTIAL WIRING OF 2 ROOMS
 
(2) 10/24/2016 10/25/2016 BMP C R (5) (0)
INSPECTION COMMENTS: OBJECTION REMOVED. CERTIFIED.

OBJECTION FOR APPLICATION #: M375690
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 023)15 KVA XFMR OVERCURRENT DEVICE NOT SIZED PROPERLY 110.3B
RSLV 10/19/2016 10/19/2016 10/24/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.