BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M179797
NO MARQUEE RECORDS FOUND FOR THIS PROPERTY
Premises: 96 BOWERY MANHATTAN BIN: 1003134     Block: 239   Lot: 35
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 96 BOWERY Census Tract:   41 Health Area:  6800
1ST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10013 Community Board:   102
DOB Cross Street(s):   HESTER STREET,    GRAND STREET
Status:   C - JOB IS SIGNED OFF 04/27/2016
Request Type:   C - COMPLAINT eFiled:   YES
Application Entered:   04/12/2016 Job Start Date:   04/12/2016
Last Change:   04/27/2016 Job End Date:   07/30/2016
Appointment Status:   
Last Inspection By:   WEISBART, F.       On     04/16/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011440 Licensee Name: MARIO F CASTRO
Firm: 004009 Firm Name: POWER SURGE ELECTRIC, INC
Firm Phone: 718-276-9797  Firm Address: 122-20 MONTAUK STREET SPRINGFIELD GARDENS NY 11413 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $46.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LULU L TENG
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    10  10    10             
Buildings Total 10  10    10                
Total Units : 35 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  08/31/1999
Power Issued: Response: F - FILED TO REMOVE OBJECTION 04/12/2016

Follow-Up: X - FILED APPL,NOW CLOSED 04/12/2016
Contractor's Comments:  STARTED BY OTHER, COMPLETED BY US

 
Inspection Details
 

*NO MARQUEE RECORDS FOUND FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M179797
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/12/1999 07/16/1999 GO1 W (60) (13)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(2) 04/16/2016 04/18/2016 FWE C R (15) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M179797
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(ALL FLOORS) SERV TROUGH,END BOX S/SW'S
RSLV 07/12/1999 07/12/1999 04/16/2016
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(ALL FLOORS) GRND CLAMP RACEWAY UNDERSIZED-RUSTED
RSLV 07/12/1999 07/12/1999 04/16/2016
 
003 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ALL FLOORS) BSMT HALLS,THRU OUT
RSLV 07/12/1999 07/12/1999 04/16/2016
 
004 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ALL FLOORS) BSMT SERV D SW'S
RSLV 07/12/1999 07/12/1999 04/16/2016
 
005 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
(ALL FLOORS) BSMT HALLS
RSLV 07/12/1999 07/12/1999 04/16/2016
 
006 ( 17) DEFECTIVE SWITCHES ARE IN USE
(ALL FLOORS) BSMT SERVICE & D SW'S-EQUIPT RUSTED & DETERIORATED
RSLV 07/12/1999 07/12/1999 04/16/2016
 
007 ( 19) DEFECTIVE WIRING IS IN USE
(ALL FLOORS) BSMT SERV & D SW'S
RSLV 07/12/1999 07/12/1999 04/16/2016
 
008 ( 26) ARMORED CABLES ARE INSTALLED EXPOSED
(ALL FLOORS) BSMT & HALL THRU OUT
RSLV 07/12/1999 07/12/1999 04/16/2016
 
009 ( 29) OUTLET BOXES ARE NOT COVERED
(ALL FLOORS) END BOX,TROUGHING
RSLV 07/12/1999 07/12/1999 04/16/2016
 
010 ( 30) OUTLET BOXES ARE NOT SECURED
(ALL FLOORS) TROUGHING-BSMT
RSLV 07/12/1999 07/12/1999 04/16/2016
 
011 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(ALL FLOORS) BSMT D SW'S
RSLV 07/12/1999 07/12/1999 04/16/2016
 
012 (999) OTHER
(ALL FLOORS) 200A D SW 3024.C DO UBLE LUGGING
RSLV 07/12/1999 07/12/1999 04/16/2016
 
013 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ALL FLOORS) SERV EQUIPT,DIS SWITCHES NOT WATER PROOF
RSLV 07/12/1999 07/12/1999 04/16/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order