BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M373328
NO MARQUEE RECORDS FOUND FOR THIS PROPERTY
Premises: 30 GROVE STREET MANHATTAN BIN: 1010010     Block: 588   Lot: 12
   

DOB NOW: Inspections


Filed: 30 GROVE ST Census Tract:   73 Health Area:  6400
BEDFORD ST. Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   BEDFORD STREET,    BLEECKER STREET
Status:   K - CLOSED/CANCELLED 01/20/2021
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/07/2015 11:45 AM
Application Entered:   10/07/2015 Job Start Date:   10/12/2015
Last Change:   01/20/2021 Job End Date:   10/12/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   SHERON MEYERS       On     01/20/2021      
Field Disp:   K - OK TO CANCEL
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011684 Licensee Name: MIKHAIL BEKKERMAN
Firm: 003267 Firm Name: STAR ELEC'L CONTRACTORS C
Firm Phone: 718-208-8231  Firm Address: 110 SHORE BLVD SUITE 5J BROOKLYN NY 11235 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CARLOS LITTLE
Owner Business Name: 30 GROVE ST., LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  125.00
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/29/2020
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ONE NEW PASSENGER ELEVATOR.

 
Inspection Details
 

*NO MARQUEE RECORDS FOUND FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M373328
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/28/2020 10/29/2020 DWB V (45) (2)
INSPECTION COMMENTS: INSPECTION COMPLETE, OBJECTION ISSUED.
 
(2) 01/14/2021 01/15/2021 LV1 C R (40) (0)
INSPECTION COMMENTS: PASS
 
(3) 01/20/2021 01/20/2021 SWR K (20) (0) Y
INSPECTION COMMENTS: PASS. INSPECTION COMPLETE WITH APP # M00441976.

OBJECTION FOR APPLICATION #: M373328
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS) 620.24, BRANCH CIRCUIT FOR HOIST WAY PIT LIGHTING ANDRECEPTACLE(S), NOT PROVIDED/ INSTALLED.
RSLV 10/28/2020 10/28/2020 01/14/2021
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(BASEMENT)EQUIPMENT GROUNDING AND EQUIPMENT GROUNDING CONDUCTOR FIXED IN PLACE250.110, AT 30 AMP DIS SW, EQUIPMENT GROUNDING CONDUCTOR NOT BONDED.
RSLV 10/28/2020 10/28/2020 01/14/2021