BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z127845
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 656 AMSTERDAM AVENUE MANHATTAN BIN: 1033613     Block: 1240   Lot: 29
   
Application Completed and Certified

Filed: 664 AMSTERDAM AV Census Tract:   1790 Health Area:  3120
BASEMENT Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10025 Community Board:   107
DOB Cross Street(s):   WEST 92 STREET,    WEST 93 STREET
Status:   C - JOB IS SIGNED OFF 02/18/2011
Request Type:   P - PICK-UP eFiled:   YES
Application Entered:   11/04/2010 Job Start Date:   11/09/2010
Last Change:   02/18/2011 Job End Date:   11/12/2010
Appointment Status:   
Last Inspection By:   CHARLES COURTNEY       On     02/15/2011      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011728 Licensee Name: HOWARD WEISS
Firm: 002455 Firm Name: H. & L. ELECTRIC INC
Firm Phone: 718-361-6400  Firm Address: 41-11 28TH STREET LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $40.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 92 EQUITIES LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                       
Buildings Total                       
Total Units : 1 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  10/05/2010
Power Issued: Response: F - FILED TO REMOVE OBJECTION 11/04/2010

Follow-Up: X - FILED APPL,NOW CLOSED 11/04/2010
Contractor's Comments:  WATER GROUND JOB 080450

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: Z127845
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/28/2010 10/05/2010 JSB W (15) (2)
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 02/15/2011 02/18/2011 CCH C R (60) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z127845
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
S.V.C.GROUND RACEWAY NOT CONTINUOUS...... 250.64E
RSLV 09/28/2010 09/28/2010 02/15/2011
 
002 (999) OTHER
S.V.C.ELECTRODE COND NOT SUPPORTED...... 250*RE: Z122788*......... - *NOT FINAL*
RSLV 09/28/2010 09/28/2010 02/15/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.