NO JOBS FOUND WITH YOUR CRITERIA
Premises: 1100 LEXINGTON AVENUE MANHATTAN BIN: 1043192     Block: 1412   Lot: 16
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 1104 LEXINGTON AV Census Tract:   140
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10075 Community Board:   108
DOB Cross Street(s):   EAST 77 STREET,    EAST 78 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   11/14/2017 Job Start Date:   10/15/2017
Last Change:   08/22/2025 Job End Date:   01/15/2018
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   ALGERNON CHARLES       On     07/18/2019      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 010738 Licensee Name: GEORGE FOTAKOS
Firm: 001971 Firm Name: ATHENS ELECTRIC INC.
Firm Phone: 718-234-9193  Firm Address: 1980 63RD STREET BROOKLYN NY 11204 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $3,193.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (9  Stores, 20 Apartments)
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   54571     Submittal #: 17A0401  
Owner / Occup: WILLIAM FRIEDLAND
Owner Business Name: FRIEDLAND PROPERTIES
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200A
C. 201 Up to 600 AMPS  2  400A
D. 601 Up to 1200 AMPS  3  2-800A,1-1200A
E. Over 1200 AMPS  1  2000A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  20  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  1 SET 3/0
D. Over 250 MCM  10  10 SETS 600MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  20  40AMP-2 POLE
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    20      24  30         
BAS                   
Buildings Total 20      24     32           
Total Units : 84 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 20 #4-Wire 1 #10-Wire 2
Existing Meters 29 + New Meters 23 - Removed Meters 23 = Total Meters 29

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 11/14/2017 Notice: 1 - FIRST NOTICE 07/19/2019
Power Issued: 11/14/2017 Response:  

Follow-Up:
Contractor's Comments:  INSTALLING A NEW SWITCHGEAR. LOAD SIDE RISERS BEING TERMINATED & CONNECTED BY DIFFERENT ELECTRICAL CONTRACTOR

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: M404129
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/18/2019 07/19/2019 AYC V (122) (14)
INSPECTION COMMENTS: FAIL. OBJECTIONS ISSUED.

OBJECTION FOR APPLICATION #: M404129
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (123) SERVICE DISCONNECTS ARE NOT PROPERLY GROUPED/LABELED
(CELLAR) ART. 230.2(E) SERVICE SWITCH #6 IS NOT IDENTIFIED
OPEN 07/18/2019 07/18/2019
 
002 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(CELLAR) ART. 110.16 EQUIPMENT MISSING ARC FLASH LABELS
OPEN 07/18/2019 07/18/2019
 
003 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(CELLAR)AMEND 110.2(B) 3/0 GROUND ELECTRODE BUS NOT INSTALLED AS PER REV. #2PLANS AT THE 2,000 AMP S.S.
OPEN 07/18/2019 07/18/2019
 
004 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(CELLAR)AMEND 110.2(B) LOAD SIDE OF THE 2,000 AMP S.S. NOT INSTALLED AS PERREV. #2 PLANS
OPEN 07/18/2019 07/18/2019
 
005 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(CELLAR)AMEND 110.2 RETAIL STORE FUSING NOT INSTALLED AS PER REV. #2 PLANS.
OPEN 07/18/2019 07/18/2019
 
006 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(CELLAR)AMEND 110.2 FEEDS FOR RETAIL STORE AND "BUTTERFIELDS" DISCONNECTSNOT SIZED AS PER REV. # 2 PLANS.
OPEN 07/18/2019 07/18/2019
 
007 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(CELLAR)ART. 230.7 SERVICE AND LOAD SIDE WIRING ARE LOCATED IN THE SAME WIREWAY OF S.S. # 5
OPEN 07/18/2019 07/18/2019
 
008 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(CELLAR) ART. 250.24 NEUTRAL IS NOT GROUNDED IN S.S. #5
OPEN 07/18/2019 07/18/2019
 
009 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(CELLAR)AMEND 110.2 LOAD SIDE OF THE 60 AMP FIRE ALARM SERVICE SWITCH IS NOTINSTALLED AS PER REV #2 PLANS
OPEN 07/18/2019 07/18/2019
 
010 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(CELLAR)ART. 314.29 GROUNDING AND MAIN BONDING JUMPER IN S.S. #4 ARE NOTACCESSIBLE
OPEN 07/18/2019 07/18/2019
 
011 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(CELLAR)AMEND 110.2 60 AMP FIRE ALARM SERVICE SWITCH NOT INSTALLED AS PERREV #2 PLANS
OPEN 07/18/2019 07/18/2019
 
012 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(CELLAR)AMEND 110.2 P.L.P. PANEL FUSING NOT INSTALLED AS PER REV #2 APPROVEDPLANS
OPEN 07/18/2019 07/18/2019
 
013 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(CELLAR)ART. 240.21 "BUTTERFIELDS" 400 AMP TAP NOT INSTALLED AS PER THE 25'TAP RULE SPECS.
OPEN 07/18/2019 07/18/2019
 
014 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(CELLAR) AMEND 110.2 FIRE PUMP IS NOT FUSED AS PER THE REV. #2 PLANS
OPEN 07/18/2019 07/18/2019