Electrical Application Details for App #: A347189
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 25-01 36 AVENUE QUEENS BIN: 4004017     Block: 339   Lot: 21
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 25-09 36TH AV Census Tract:   47 Health Area:  0710
BASEMENT Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11106 Community Board:   401
DOB Cross Street(s):   CRESCENT STREET,    28 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/21/2016 4:57 PM
Application Entered:   03/21/2016 Job Start Date:   03/21/2016
Last Change:   08/22/2025 Job End Date:   03/20/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   SCHUSZTER, NORBET       On     05/03/2017      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 012247 Licensee Name: MICHAEL MARCELLE
Firm: 003992 Firm Name: LIDMAR ELEC SERVICES CORP
Firm Phone: 718-363-1800  Firm Address: 1562 ATLANTIC AVENUE BROOKLYN NY 11213 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $640.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   K1-STORE BUILDING
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOHN CIAFONE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  -
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  600A
D. 601 Up to 1200 AMPS  0  -
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  7  4 - #3AWG
B. Over #2 to 1/0  1  4 - #1AWG
C. Over 1/0 to 250 MCM  1  4 - 2/0
D. Over 250 MCM  4  4- 350MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  24 CIRCUIT PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL                       
Buildings Total                       
Total Units : 9 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 10 #10-Wire 0
Existing Meters 10 + New Meters 10 - Removed Meters 10 = Total Meters 10

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 03/21/2016 Notice: 1 - FIRST NOTICE 05/03/2017
Power Issued: 03/21/2016 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: A347189
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/15/2016 11/15/2016 NRS V (74) (11)
INSPECTION COMMENTS: OCPD SIZE OF EXISTING 200A SWITCH WITH NEW #1AWG FEEDERS NEEDS VERIFICATION. NO PANEL INSTALLED.
 
(2) 05/03/2017 05/03/2017 NRS V Y (76) (3)
INSPECTION COMMENTS: SEE PREVIOUS NOTES.

OBJECTION FOR APPLICATION #: A347189
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(CELLAR) IN SERV. DISC. & END LINE BOX NOT SIZED AS PER 250.66
RSLV 11/15/2016 11/15/2016 05/03/2017
 
002 (109) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(CELLAR) FRONT OF 600A SERV. DISC.
OPEN 11/15/2016 11/15/2016
 
003 (125) PROTECTION OF CONDUCTORS NOT INSTALLED AS PER CODE
(CELLAR) NEW 200A DISCONNECT
OPEN 11/15/2016 11/15/2016
 
004 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(CELLAR) IN ALL (9) SECONDARY 100A & 200A SWITCHESSWITCHES
RSLV 11/15/2016 11/15/2016 05/03/2017
 
005 (129) SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
(CELLAR) 600A SERV. DISC.
OPEN 11/15/2016 11/15/2016
 
006 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(CELLAR) IN 600A SERV DISC. NOT SIZED AS PER 250.122
OPEN 11/15/2016 11/15/2016
 
007 ( 19) DEFECTIVE WIRING IS IN USE
(CELLAR) LOAD SIDE PARALLEL 350-S NOT AS PER 310.4
OPEN 11/15/2016 11/15/2016
 
008 ( 19) DEFECTIVE WIRING IS IN USE
(CELLAR)#1AWG TAP FEEDER FOR EXISTING 200A DISC. LONGER THAN 10' 240.21
OPEN 11/15/2016 11/15/2016
 
009 ( 19) DEFECTIVE WIRING IS IN USE
(CELLAR) GEC NOT SUPPORTED
RSLV 11/15/2016 11/15/2016 05/03/2017
 
010 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(CELLAR) NOT SIZED AS PER 250.66
RSLV 11/15/2016 11/15/2016 05/03/2017
 
011 (999) OTHER
(CELLAR) 600A SERV. DISC NOT MARKED
RSLV 11/15/2016 11/15/2016 05/03/2017
 
012 (125) PROTECTION OF CONDUCTORS NOT INSTALLED AS PER CODE
(BASEMENT)CORNER 100A DISCONNECT (3557 CRECENT) OVERFUSED, 100AOCPD ON #6AWG
OPEN 05/03/2017 05/03/2017
 
013 ( 19) DEFECTIVE WIRING IS IN USE
(BASEMENT)IN TROUGH: MULTIPLE CONDUCTORS UNDER SPLIT BOLTS & IN INDIVIDUALHOLES OF POLARIS CONNECTORS 2110.14
OPEN 05/03/2017 05/03/2017
 
014 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(BASEMENT) CONDUIT TO EXISTING 200A DISCONNECT
OPEN 05/03/2017 05/03/2017